Rccmd Command Group - GE Digital Energy 1018959 Operating Manual

Snmp / web adapter
Hide thumbs Also See for Digital Energy 1018959:
Table of Contents

Advertisement

(*) By running these commands, an interactive menu is launched – follow the on-screen instructions.
The menu also provide a complete on-line help section.
NOTE: When using the local serial connection, make sure that the terminal emulation is set to VT-100,
otherwise the interactive menu may not be rendered correctly.
Caution! Some of these commands (particularly upscontrol and upsconfig) may inject commands
and/or alter the UPS configuration with consequences on the UPS operation that may affect the load.
Make sure you fully understand the effect on the UPS and on the load before injecting any of these
commands. Make sure that it is safe to perform the desired operation for both the UPS and the load.

2.2.11 Rccmd command group

The rccmd command group allows to configure the RCCMD Server embedded in the SNMP/Web
adapter.
Command
Sub-command
showrccmd
add
rccmd
test
del
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc
Parameters
on|off
[ip]
[port]
[cond]
[num]
[num]
Description
Shows
the
current
configuration
Enable/disable Network Shutdown function
on
Network Shutdown enabled
off
Network Shutdown disabled)
Add an RCCMD Client
[ip]
IP-address of the trap target
[port] Port on which the client is listening
[cond] Shutdown condition:
aXX
after XX minutes on battery
bXX
at XX min remain batt time
Send an RCCMD test message to a specific
RCCMD client
[row]
RCCMD client reference
Delete an RCCMD Client
[row]
RCCMD client reference
RCCMD
Server
Page 24/58
Operating Manual SNMP/Web Adapter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents