INSTALLER SETUP

NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the
factory settings in Table 2 and if no changes are
necessary, go to the Installer System-Test
section.
The Installer Setup is used to customize the thermostat to
specific systems. Some of the options include temperature
display, changeover, minimum equipment on time and
minimum off time. Installer numbers are listed in Table 2.
The table includes all the configuration options and the
factory-settings available for the T8511.
IMPORTANT
The Installer Setup must be set correctly for the
HVAC equipment, thermostat and subbase to
operate properly.
A combination of key presses are required to use the
Installer Setup feature.
— To enter the Installer Setup, press and hold the
Information i key with the increase
keys until the first number is displayed. All display
segments appear for approximately three seconds
before the number is displayed. See Figs. 11 and 12.
— To advance to the next Installer Setup, press the
Information i key.
— To change a setting, use the increase
key.
— To exit the Installer Setup, press and hold the
Information i key until the display returns to normal
(approximately three seconds). The display scrolls the
numbers backwards to get to the normal display. The
Installer Setup is automatically exited if no key
presses are made for five minutes.
Installer Setup
Number
(Press i key
to change)
Select
Not used
01 thru 04
Heating cycle
05
rate
06
07
Not used
08 thru 11
Changeover
12
(T8511G only)
Not used
13
Degree
14
temperature
display
Not used
15 thru 18
a
The cycle rate for the last stage of heat is adjustable with 6 being the factory setting.
T8511G,R MICROELECTRONIC HEAT PUMP THERMOSTATS
and decrease
or decrease
Table 2. Thermostat Installer Setup Options.
Factory-Setting
Display
Description
03
Stage 2
Not used
09
Emergency heat
01
Manual changeover
00
Temperature is
displayed in °F
Em Ht Temporary Setting
Aux Ht
Repl
Wait
Batt
System
Em HeatOffCool Auto Only
Fig. 11. Display of all the segments of the LCD.
Fig. 12. Display of Installer Setup and setting.
NOTE: Only configurable numbers are shown.
Other Choices
(Press
Display
03, 06
03—3 cph used for stage 1
or 09
heat pump systems
06—6 cph used for
conventional systems
09—9 cph used for electric
heat systems
00, 02
00—Automatic changeover
02—Automatic changeover
only
01
Temperature is displayed in
°C
5
Remote
Room
%Humid
Outdoor
Heat Cool
Fan
OnAuto
INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2 OF TABLE 2)
FACTORY SETTING OR
OTHER CHOICE DISPLAY
(COLUMN 3 OR 5 OF TABLE 2)
or
key to change)
Description