Venting - Kenmore 153.332110 Owner's Manual

Gas water heater
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Venting (cont'd)
Gas Piping
All vent gases must be completely
vented to the outdoors
of the
structure (dwelling).
Instal/only
the draft hood provided with
the new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal screws.
1
VENT
PIPE INSTALLATION
TO
CHIMNEY
A WARNING
Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed
10.5 in. water column (2.6kPa) for natural gas or 13 in. water
column (3.2kPa) for propane (L.P.) gas. The minimum inlet
gas pressure listed on the model rating plate is for the pur-
pose of input adjustment.
AWARNING
,1
If the gas control valve is subjected to pressures exceeding ½J
pound per square inch (3.5kPa), the damage to the gas con-J
trol valve could result in a fire or explosion from leaking gas. ]
AWARNING
If the main gas line shutoff serving all gas appliances is used,
also turn "OFF" the gas at each appliance. Leave all gas appli-
ances shut off until the water heater installation iscomplete.
There must be a minimum
of 6" clearance
between single wall
vent pipe and any combustible
material. Fill and seal any clear-
ance between
single wall vent pipe and combustible
material
with mortar mix, cement,
or other noncombustible
substance.
For other than single wall, follow vent pipe manufacturer's clear-
ance specifications.
To insure a tight fit of the vent pipe in a
brick
chimney,
seal around
the vent pipe with
mortar mix
cement.
AWARNING
I
Failure to have required clearances between vent piping and
combustlb e material wi I resu t n a fire hazard.
AWARNING
J
Be sure vent pipe is properly connected to prevent escape of
dangerous flue gaseswh ch cou d cause deadly asphyxiation.
AWARNING
Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator
and air
conditioner refrigerants,
swimming pool chemicals, calcium
i and sodium chloride, waxes, bleach, and processchemicals are
typical compounds which are potentially corrosive.
A gas line of sufficient
size must be run to the water heater.
Consult
the latest edition
of National
Fuel Gas Code ANSI
Z223.1, also referred to as NFPA54 and the gas company concern-
ing pipe size.
There must be:
• A readily accessible manual shut off valve in the gas supply line
serving the water heater, and
• A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
Valve.
• A flexible gas connector
or a ground joint union between the
shutoffvalve
and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting
the
water heater. Use a soapy water solution,
not a match or open
flame. Rinse offsoapy solution and wipe dry.
Standard
Models are for installation
up to 3,300 feet above sea
level.
High Altitude
Models are for installation
from 3,300 to 5,500
feet above sea level.
Ifa standard model is installed above 3,300 feet or a high altitude
model is installed
above 5,500 feet, the input
rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact
your local Sears Service Center
or gas utility for further
information.
f
A WARNING
The appliance and it_
must be leak tested
before placing the appliance in operation.
14

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents