4–22
Using Intelligent Output Terminals

Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is in
Run Mode. The output logic is active low, and
is the open collector type (switch to ground).
Option
Terminal
Code
Symbol
00
RUN
Valid for outputs:
Required settings:
Notes:
The inverter outputs the [RUN] signal whenever the
inverter output exceeds the start frequency specified
by parameter B_82. The start frequency is the initial
inverter output frequency when it turns ON.
NOTE: The example circuit in the table above drives a relay coil. Note the use of a
diode to prevent the negative-going turn-off spike generated by the coil from damaging
the inverter's output transistor.
Output
Function Name
State
Run Signal
ON
OFF
11, 12
(none)
[FW],
1
[RV]
0
B 82
Output
start freq.
freq.
Run
1
Signal
0
Description
when inverter is in Run Mode
when inverter is in Stop Mode
Example (default output configuration
shown—see page 3–36):
Inverter output
terminal circuit
H O OI
L
See I/O specs on page 4–6.
ON
t
RUN
FM CM2
12 11
+
RY