How
to use the receptacles
When two or more receptacles are used, refer to the table below and apply
the load to each receptacle
equally to prevent overloading.
Voltage fluctuation
can be prevented
by applying the load equally to the
single phase receptacles.
240 V
120v
50 A
30 A
50 A
30 A
20 A Max.
for both
Using 240 V only
41.7 A Max.
30 A Max.
41.7 A Total
Using 120 V only
50 A Max.
30 A Max.
20 A Max.
at one -
Total 83.4 A
Using both 120 V
Total 10 A
Total 63.3 A
and 240 V
Total 20 A
Total 43.3 A
-
Total 30 A
Total 23.3 A
When both 240 V and 120 V receptacles are used, be sure that the ampere
draw at each receptacle
is less than the specified
capacity
and the total
ampere(s) are less that 83.4 amperes.
WOV20A
120V30A
22
-0,
120 VI240 V 50 A