6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe
6-1. Model: AOU9RL2
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than outdoor
unit *
Indoor unit is lower than outdoor
unit *
HEATING
Indoor unit is higher than outdoor
unit *
Indoor unit is lower than outdoor
unit *
6-1. Model: AOU9RL2
Height difference H
*
H
Outdoor unit
m
15
10
1
7.5
5
0
-5
-7.5
2
-10
-15
m
15
10
1
7.5
5
0
-5
-7.5
2
-10
-15
1
Indoor unit is lower than outdoor unit
Outdoor unit
Connection pipe
Pipe length
5
7.5
ft
17
25
50
—
—
33
—
—
25
—
0.988
17
1.003
0.992
0
1.011
1.000
-17
1.011
1.000
-25
—
1.000
-33
—
—
-50
—
—
Pipe length
5
7.5
ft
17
25
50
—
—
33
—
—
25
—
1.000
17
1.014
1.000
0
1.014
1.000
-17
1.009
0.995
-25
—
0.993
-33
—
—
-50
—
—
- 33 -
6. Capacity compensation rate for pipe length and height difference
2
*
H
Indoor unit
10
15
20
33
50
67
—
0.901
0.920
0.969
0.916
0.936
0.973
0.919
0.939
0.976
0.923
0.943
0.984
0.931
0.951
0.984
0.931
0.951
0.984
0.931
0.951
0.984
0.931
0.951
—
0.931
0.951
10
15
20
33
50
67
—
0.904
0.898
0.976
0.904
0.898
0.976
0.904
0.898
0.976
0.904
0.898
0.976
0.904
0.898
0.971
0.900
0.894
0.968
0.898
0.892
0.966
0.895
0.889
—
0.886
0.880