1-1. COOLING OPERATION

A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature,
and controls the operation speed of the compressor.
* If the room temperature is 2 °C higher than a set temperature,
the compressor operation speed will attain to maximum speed.
* If the room temperature is some degree lower than setting temperature,
the compressor is likely to stop.
* When the room temperature is between +2 °C to -2.5 °C of the setting temperature,
the compressor speed is controlled within the range shown in Table 1.
However, the maximum speed is limited in the range shown in Figure 1 based
on the fan speed mode and the outdoor temperature.
( Table 1 : Compressor Speed Range )
AO*A30LFTL
AO*A36LFTL
AOTA30LGTL
( Fig.1 : Limit of Maximum Speed based on Outdoor Temperature )
Outdoor air
temperature
34°C
30°C
19°C
10°C
0°C
When the room
temperature drops
Fan speed mode
AO*A30LFTL
AO*A36LFTL
AOTA30LGTL
minimum
maximum
speed
speed
16rps
72rps
A zone
B zone
C zone
D zone
E zone
F zone
When the room
temperature rises
Hi
Me
A zone
72rps
50rps
B zone
72rps
50rps
C zone
56rps
42rps
D zone
42rps
37rps
E zone
42rps
37rps
F zone
42rps
37rps
01-01
36°C
32°C
21°C
12°C
2°C
Lo
Qu
42rps
29rps
42rps
29rps
37rps
29rps
32rps
20rps
32rps
20rps
32rps
20rps