Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible
temperature of conductor in continuous use. For North America, power cables
must be rated for 75 °C (167 °F) or higher.
Note: For drives with option +B056 (IP55, UL Type 12), select a cable rated for at
least 90 °C (194 °F) maximum permissible temperature of conductor in continuous
use.
Note: For drives with option +B063 or +B066 (IP66, UL Type 4X), with voltage rating
575 V AC (-6) running above 40 °C ambient temperature, select a cable rated of at
least 90 °C (194 °F) maximum permissible temperature of conductor in continuous
use.
Voltage: 600 V AC cable is accepted for up to 500 V AC.
Terminal and entry data for the control cables
■
IEC
Control cable entries, wire sizes and tightening torques ( T ) are given below.
Frame
Cable entries
size
Holes
pcs
R1
3
R2
3
R3
3
R4, R4
4
v2
R5
3
R6
4
R7
4
R8
4
R9
4
Frame size
Max cable
+24V, DCOM, DGND, EXT.
size
24V terminals
Wire size
mm 2
mm
17
0.2...2.5
17
0.2...2.5
17
0.2...2.5
17
0.2...2.5
17
0.2...2.5
17
0.14...2.5
17
0.14...2.5
17
0.14...2.5
17
0.14...2.5
R9
Control cable entries and terminal sizes
T
N·m
0.5...0.6
0.5...0.6
0.5...0.6
0.5...0.6
0.5...0.6
0.5...0.6
0.5...0.6
0.5...0.6
0.5...0.6
Technical data 341
Cu cable type
AWG/kcmil
2×250 MCM
DI, AI/O, AGND, RO, STO
terminals
T
Wire size
mm 2
N·m
0.14...1.5
0.5...0.6
0.14...1.5
0.5...0.6
0.14...1.5
0.5...0.6
0.14...1.5
0.5...0.6
0.14...1.5
0.5...0.6
0.14...2.5
0.5...0.6
0.14...2.5
0.5...0.6
0.14...2.5
0.5...0.6
0.14...2.5
0.5...0.6