Download Print this page

Zennio Lumento DX4 v2 Technical Documentation

Advertisement

Quick Links

4-channel constant voltage PWM dimmer in DIN rail for DC LED loads
ZDILDX4V2
FEATURES
4
constant
independent channels, RGBW channel, RGB+W channels and
combinable TW channels)
1 relay to control the LEDs power supply or for independent use
Supports KNX Data Secure
Master Light control
External 12-40 VDC power supply
Manual output operation with push button and LED status indicator
Total data saving on KNX bus failure
Integrated KNX BCU (TP1-256)
Dimensions 67 x 90 x 79 mm (4.5 DIN units)
DIN rail mounting according to IEC 60715 TH35, with fixing clamp
Conformity with the CE, UKCA, RCM directives (marks on the right
side)
1. Power Supply LED
6. (not used)
11. KNX connector
Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe mode.
If this button is held for more than 3 seconds, the device enters the test mode. In order to perform a KNX Secure factory reset, while the device is in safe
mode, press the button for 10 seconds until the programming LED changes its state.
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The test mode is
indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
GENERAL SPECIFICATIONS
CONCEPT
Type of device
Voltage (typical)
Voltage range
KNX supply
Maximum
consumption
Connection type
External power supply
Operation temperature
Storage temperature
Operation humidity
Storage humidity
Complementary characteristics
Protection class / Overvoltage category
Operation type
Device action type
Electrical stress period
Degree of protection
Installation
Minimum clearances
Response on KNX bus failure
Response on KNX bus restart
Operation indicator
Weight
PCB CTI index
Housing material
¹ Maximum consumption in the worst-case scenario (KNX Fan-In model).
© Zennio Avance y Tecnología S.L.
voltage
configurable
channels
2. Colour shift control buttons
7. Relay status LED
12. Programming/Test LED
Voltage
29 VDC (typical)
24 VDC¹
Edition 1
(combinable
3. External power supply
8. Relay control button
13. Programming/Test button
DESCRIPTION
Electric operation control device
29 VDC SELV
21-31 VDC
mA
6.2
10
Typical TP1 bus connector for 0.8 mm Ø rigid cable
12-40 VDC
0 .. +55 °C
-20 .. +55 °C
5 .. 95%
5 .. 95%
Class B
II / III (4000 V)
Continuous operation
Type 1
Long
IP20, clean environment
Independent device to be mounted inside electrical panels with DIN rail (IEC
60715)
Not required
Data saving according to parameterization
Data recovery according to parameterization
The programming LED indicates programming mode (red) and test mode
(green). Color shift LEDs show the current color. Each output LED indicates
its status.
200 g
175 V
PC FR V0 halogen free
Further information
Lumento DX4 v2
TECHNICAL DOCUMENTATION
1
2
3 4
5
6
15
14 10
13 12 11
Figure 1: Lumento DX4 v2
4. Colour output LEDs
9. Power Supply Relay
14. Channel status LED
15. Channel control button
mW
179.2
240
www.zennio.com
7
8
9
10
5. TW selection button
10. Output channels
Page 1/2

Advertisement

loading

Summary of Contents for Zennio Lumento DX4 v2

  • Page 1 • DIN rail mounting according to IEC 60715 TH35, with fixing clamp • Conformity with the CE, UKCA, RCM directives (marks on the right Figure 1: Lumento DX4 v2 side) 1. Power Supply LED 2. Colour shift control buttons 3. External power supply 4.
  • Page 2 • The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructi ons at https://www.zennio.com/en/legal/weee-regulation. This device contains software subject to specific licences. For details, please refer to https://zennio.com/licenses. © Zennio Avance y Tecnología S.L.