Appendix 8
Appendix 8.1
Refer to the following manual.
MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection)
Appendix 8.2
The following shows the operating method to use the GX Developer.
For details on the operation of GX Developer, refer to the
(1) How to operate the wiring check
[Example of wiring check]
Specify the "Remote input (RX)" for the master station to "X1000" and the "Remote output (RY)" to "Y1000" with
the GX Developer.
Master station
(a) Checking the wiring between the input module and an external device
1.
Turn ON the switch corresponding to the external device "X0," which is connected to the input
module of station number 1.
2.
Using the GX Developer, set "X1000" in the "Device:" field by choosing [Online]
[Device batch] and then click on "Start monitor".
3.
If X1000 is ON, the connection between the input module and external device has been properly
performed.
(b) Checking the wiring between the output module and an external device
1.
Using the GX Developer, set "Y1020" in the "Device:" field for the "Bit device" by choosing
[Online]
2.
If the connection between the output module and external device is properly performed, the
indicator lamp corresponding to the external device "Y00" is lit.
When Using the GX Developer
Compatible software package
Operation comparison
Input module
Remote I/O station
(Station number 1, number
of occupied stations 1)
X00
[Debug]
[Device test] and then click on "FORCE ON".
Operating Manual of GX Developer.
Output module
Remote I/O station
(Station number 2, number
of occupied stations 1)
ON
Y00
APPENDICES
ON
[Monitor]