5. WIRELESS KIT
FDT series(RCN-T-5BW-E2, RCN-T-5BB-E2)
12. OPTION PARTS
(1) Specification
12.1 Wireless kit
(1) FDT series(RCN-T-5BW-E2, RCN-T-5BB-E2)
(a) Specification
Receiver
205
Setting switch on PCB of receiver
Prevent interference
SW1
during plural setting
Receiver master/
SW2
slave setting
Buzzer
SW3
Auto restart
SW4
Default setting:
Remote control
60
Installation position of wireless kit
Refrigerant pipe
Notes
(1)Receiver can install the position as shown.
ON:Normal
(2)Two LR03 AAA dry cell batteries for remote
OFF:Remote
control are enclosed.
ON:Master
(3)See spec sheet of "Wireless remote control"
OFF:Slave
about remote control.
ON:Valid
OFF:Invalid
ON:Valid
OFF:Invalid
mark
Remote control holder
65
24
Receiver
Drain pipe
32.5
293
-
-
- 18 -
Installation of wireless kit
Do not install the wireless kit at the following places
in order to avoid malfunction.
(1)Places exposed to direct sunlight
(2)Places near heat devices
(3)High humidity places
(4)Hot surface or cold surface
enough to generate condensation
(5)Places exposed to oil mist or steam directly
(6)Uneven surface
(7)Places affected by the direct airflow of the AC
unit
(8)Places where the receiver is influenced
by the fluorescent lamp(especially inverter type)
or sunlight
(9)Places where the receiver is affected by infrared
rays of any other communication devices
(10)Places where some object may obstruct the
communication with the remote control
Wireless remote control's operable area
Standard reachable area of the signal
1
[condition] Illuminance at the receiver:300lux
(When no lighting is installed within 1m of the
receiver in an ordinary office.)
Correlation between illuminance at the receiver and
2
reachable area of the signal in a plain view.
The drawing in the right shows the correlation between the
reachable area of the signal and illuminance at the receiver
when the remote control is operated at 1m high under
the condition of ceiling height of 2.4m.
When the illuminance becomes double,
the area is narrowed down to two thirds.
Installation tips when several receivers are installed close
3
Minimum distance between the indoor units which can avoid
cross communication is 5m under the condition of 300lux of
illuminance at the receiver.
(When no lighting is installed within 1m
of the receiver in an ordinary office.)