28 Air Flow Label
Menu Navigation and Selection Instructions
Using Phone Application over Bluetooth Network:
1) Connect to the air handler (instructions provided by phone during
connection process).
2) Select desired settings menu
3) Select item that requires adjustment and make necessary selection
4) Submit Changes
Using On-Board Push Buttons:
1) Use the Right and Left Buttons to scroll between menus
2) Use the Center Button to select desired menu when menu code is
shown on 7-segment displays
3) Use the Left and Right Buttons to scroll through options within the
desired menu (the display will flash while scrolling through options for
selection)
4) Use the Center Button to select the displayed option (when selected
the display will stop flashing)
5) Use the Center Button to finalize selection and return to the main
menu
Profiles
Airflow Settings Instructions
1) For non-communicating installations, select the type of unit installed
in the OdS menu (1AC = single-stage air conditioner,
1HP = single-stage heat pump, 2AC = 2 stage air conditioner,
2HP = 2 stage heat pump) Default = OFF (no outdoor unit).
2) Use the Tonnage Menu (ton ) to select Cooling/Heat Pump Airflow
(non-communicating installation). Tonnage selection options and
corresponding airflow CFM can be found to the right.
[Airflow = Tonnage Selection x 400] Default selection is 6.0 tons.
3) [Optional] Use the Cooling Trim Menu (CtF) to adjust the cooling
airflow from -10% to +10% (2% increments). This applies for 2
stage communicating outdoor units and single or 2 stage
non-communicating outdoor units.
4) [Optional] Use the Heating Trim Menu (HtF) to adjust the heat pump
airflow from -10% to +10% (2% increments). This applies for 2
stage communicating outdoor units and single or 2 stage
non-communicating outdoor units.
5) [Optional] Use the Constant Fan Menu (FSD) to select the
percentage of maximum airflow for continuous fan
6) [Optional] Use the Cooling Airflow Profile Menu (CAP) to select
between 5 cooling airflow profiles. Profile options 1-4 are listed above
(option 5 is adjustable). See installation manual for further details
Htr Kw
3
5
6
8
10
15
19
20
25
Selecting Heater Kit: Use the Electric Heating Wattage Menu (EHt) to select heater kit size. See "Menu Navigation and Selection Instructions"
above. Default selection is 0 (No Heat Kit). Select installed heater kit for heater kit operation.
NR - Not Rated
Pre-Run
Short-Run
OFF Delay
1
--------
--------
60 sec/100%
2
--------
30 sec/50% 60 sec/100%
3
--------
7.5 min/82% 60 sec/100%
4
30 sec/50%
7.5 min/82% 60 sec/100%
Electric Heat Airflow Table
AMVT30BP14
AMVT36CP14 AMVT42CP14 AMVT48CP14 AMVT48DP14 AMVT60DP14
AMVT24BP14
AMVT36BP14
550
550
650
650
700
700
800
800
850
875
875
1050
NR
NR
NR
NR
NR
NR
Tonnage Menu (t o n)
Tonnage
Selection
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.5
Maximum Airflow Output
AMVT24B*
AMVT30B*
AMVT36B*
AMVT36C*
AMVT42C*
*If airflow is set above the model's maximum value, the output will be the
maximum value
630
NR
NR
735
880
735
810
880
810
925
1045
925
1020
1020
1200
1420
1145
1145
1480
1345
1345
NR
NR
NR
NR
NR
NR
27
Tonnage
Airflow
Airflow
Selection
400
3.5
1400
440
3.6
1440
480
3.7
1480
520
3.8
1520
560
3.9
1560
600
4.0
1600
640
4.1
1640
680
4.2
1680
720
4.3
1720
760
4.4
1760
800
4.5
1800
840
4.6
1840
880
4.7
1880
920
4.8
1920
960
4.9
1960
1000
5.0
2000
1040
5.1
2040
1080
5.2
2080
1120
5.3
2120
1160
5.4
2160
1200
5.5
2200
1240
5.6
2240
1280
5.7
2280
1320
5.8
2320
1360
5.9
2360
1400
6.0
2400
1275
AMVT48C*
1700
AMVT48D*
1200
1800
1450
2200
AMVT60D*
1575
NR
NR
1135
1040
1265
1170
1260
1375
1300
1455
1595
1815
NR
NR
1595
1860
NR
1925
0140A00908-A