D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN

2.0 9000MAIN

Use this programming module to define the
operating characteristics that affect panel-wide
functions. There are nine programming categories in
this module: Phone, Phone Parameters, Routing,
Enhanced Communications, Area Parameters,
Command Center, User Interface, Function List, and
Relay Parameters.
2.1
Phone
The control panel can dial up to four different
telephone numbers when sending event reports. All
telephone numbers use the same receiver format.
Event report routing and communication protocols
are discussed in Section 2.3 Routing.

Phone 1

Default:
Blank
Selection:
Up to 24 characters (do not enter
[SPACE])
0 to 9
Numbers 0 through 9
C
3-second pause
D
7-second dial-tone detect.
# or *
Used for the same purpose as pressing
this key on a telephone keypad when
manually dialing. For example, an
asterisk (*) may be needed to access
your long distance service. Do not use
these characters when pulse dialing.
Blank
Control panel dials no phone number.
Programming this item Blank does not
disable phone routing. To disable
reporting to this phone, see Section 2.3
Routing.
This is the telephone number the control panel dials
to contact the central station receiver when sending
event reports. This number is Phone 1 referred to in
the prompts in Section 2.3 Routing.
Bosch Security Systems | 10/03 | 47775E
The control panel is pre-programmed with a
7-second dial tone detect period. When a dial tone is
detected or the waiting period ends, the control
panel begins to dial. To extend the dial tone detect
period, place a D before the phone number. To
insert a pause during or after dialing, use C in the
number sequence. For example, if the control panel
hangs up before it hears the Modem IIIa
from the D6500/D6600, program extra Cs after the
phone number. The control panel waits on line for
three extra seconds for each C programmed.
Enter up to 24 of the following characters to define
dialing characteristics.
0101
Using both phone data entry lines: The first
0101
line of the phone number data entry line
0101
must be filled (twelve characters) before
you press [ENTER] to move on to the
second line. If you enter characters on the
second line, and there are less than twelve
characters on the first line, the second line
clears when you press [ENTER].

Phone 2

Default:
Blank
Selection:
Up to 24 characters (do not enter
[SPACE])

Phone 1

See explanation of
2, referred to in the prompts in Section 2.3 Routing.

Phone 3

Default:
Blank
Selection:
Up to 24 characters (do not enter
[SPACE])
See explanation of

Phone 1

3, referred to in the prompts in Section 2.3 Routing.

Phone 4

Default:
Blank
Selection:
Up to 24 characters (do not enter
[SPACE])
Phone 1
See explanation of
4, referred to in the prompts in Section 2.3 Routing.
EN | 11
2
Ack tone
. This number is Phone
. This number is Phone
. This number is Phone

Hide quick links: