Fujitsu AIRSTAGE J-II Design & Technical Manual page 694

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

(2) When electricity meter used is specified by pulse constant
The connection configuration is shown below.
Electricity meter
pulse
transmission
Pulse constant
line
reference point
measurement
VT
line
(PT)
CT
VT
measurement
(PT)
line
Pulse constant
reference point
Electricity meter
For the electricity meter specified by pulse constant, the power consumption indicated by
output pulse must be corrected by VT/CT ratio. In this case, the settings are as follows:
Set point
Set item
Electricity
Set in
meter
accordance
with the product
manual.
Outdoor unit Meter No.
setting
Electricity meter
pulse setting
System
Electricity meter
controller
system setting
Pulse setting
*1: Input up to 6 decimal digits
[Setting example]
Equipment conditions: VT ratio=1 (not used), CT ratio=500(2500/5A), electricity meter=3200 pulse/kWh
Set value: Electricity meter pulse setting=6 (3200/ (1x500)),
Pulse setting=0.9375 (6x (1x500)/3200) ---Refer to the calculating formula of the table above.
to CN135
Outdoor unit
Power cable
Indoor unit
RB unit
Transmission line (VRF Network)
pulse transmission line
Set value
Description
-
When there is a product unique setting,
setting is performed in accordance with
the product manual. (Pulse constant
value, output coefficient, etc.)
Arbitrary
Set an unique electricity meter No. for
electricity meter identification.
The pulse constant
Set the approximate number of power
value / (VT ratio x
meter pulses that are equivalent to
CT ratio). However,
1kWh.
truncated after the
decimal point
from the electricity meter, the outdoor
unit communicates "1" to the system
controller.
Unit to be measured by
Sets the outdoor unit and indoor unit,
electricity meter
measured by the electricity meter of
the meter No. set at the outdoor unit.
(Electricity meter pulse
Set the standard number of kWh for the
setting value) x (VT
value communicated from the outdoor
ratio x CT ratio)/pulse
unit.
constant
Set the number of kWh that
Values after the
corresponds to the "1" communicated
decimal point must be
from the outdoor unit.
also input. *1
- (07-168) -
System Controller
to CN135
When set number of pulses come
Remarks
The information
will become
necessary when
setting System
Controller later.
Refer also to
Chapter 6. 2-1.
OUTDOOR
UNIT
The value set
by each outdoor
unit is used.
Refer to the
value set by
each outdoor
unit.