Technical Data
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m
RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
o
ta = 0 - 50 C
CAPACITY: Max 4 x DSI or DALI ballasts
INTERCONNECT CABLE TEMPERATURE RATING: 60 C
COLOUR: White (RAL9010) or silver bezel (DHW = White, DHS = Silver)
MATERIAL: UV stabilised polycarbonate (DHW/DHS)
Flame retardant PC/ABS (MSM2000D/DALI)
IP RATING: 20
DIMENSIONS: 32 (l) x 21 (w) x 18.6 (h) mm (DHW/DHS)
147 (l) x 30 (w) x 21 (h) mm (MSM2000D/DALI)
WEIGHT: 32g incl. 0.8m cable (DHW/DHS)
48g (MSM2000D/DALI)
Important Additional Notes
1.
A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
2.
Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains
with regard to wiring practice. The 0V line of the dimming output is almost at Neutral potential.
3.
The dimming control output should be connected only to the control input of the ballasts - never to other detectors.
4.
This equipment should be used to control only those ballasts powered from the same phase as the detector.
5.
Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on
the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent.
Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light level only.
6.
This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of
some particular lighting types (e.g. '2D' luminaires) may specify a maximum number of switching cycles in order to achieve a
predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic
controls in this respect.
7.
Some devices in this product range feature a silvered surface finish; this is intended for decorative purposes only . Care
should be taken to avoid accidental separation of the silvered coating from the product. If the unit is built into a luminaire
that is subsequently wrapped in film having adhesive properties, it is recommended that a layer of suitable packaging
material be used to protect the silvered area.
Honeywell Ex-Or
St. Marks Court, North Street, Horsham,
West Sussex, RH12 1BW, UK.
Tel: +44 (0)1942 719229
Email: ex-ortechnicalsales@honeywell.com
www.ex-or.com
2.5m
6.0m
o
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
W4267I

Advertisement

loading

This manual is also suitable for:

Ex-or msm2000daliEx-or dhwEx-or dhs