Pre-Installation; Cleaning Primary Systems; Mains Supply; Electrical Supply - Bosch Worcester Greenstar Danesmoor 12/18 Installation, Commissioning And Servicing Instruction Manual

Floor standing oil-fired condensing boiler conventional flue & room sealed flue
Hide thumbs Also See for Worcester Greenstar Danesmoor 12/18:
Table of Contents

Advertisement

4

Pre-Installation

4.1

Cleaning primary systems

NOTICE: Before installation
▶ All the following Pre-Installation sections must be
read and requirements met before starting boiler or
flue installations.
CAUTION: MAINS POWER
▶ ISOLATE THE MAINS SUPPLIES BEFORE STARTING
ANY WORK AND OBSERVE ALL RELEVANT SAFETY
PRECAUTIONS.
NOTICE: Protect the boiler
▶ Debris from the system can damage the boiler and
reduce efficiency.Failure to comply with the
guidelines for the use of water treatment with the
appliance will invalidate the appliance warranty.
▶ It is recommended that a primary water cleanser is
fitted to the system. Worcester offers a system filter
that helps remove both magnetite and non-magnetic
debris.
BEFORE CLEANING THE SYSTEM:
▶ Ensure that the system and pipe work is in good working order.
▶ Where possible keep the existing boiler/circulating pump in
place when flushing the system.
FOLLOW THE GUIDANCE OF BS7593:
Treatment of water in domestic hot water central heating and also the
flushing guidelines below.
FLUSHING THE SYSTEM
▶ Fill the system with cold water and check for leaks.
▶ Open all drain cocks and drain the system.
▶ Close drain cocks and add a suitable flushing agent at the correct
strength for the system conditions in accordance with the
manufacturer's instructions.
▶ Circulate the flushing agent before the boiler is fired up.
▶ Run the boiler/system at normal operating temperature as directed
by the manufacturer of the flushing agent.
▶ Drain and thoroughly flush the system to remove the flushing agent
and debris.
▶ It may be necessary to use a power flushing machine to aid the
cleansing procedure in some circumstances.
▶ Close the drain cocks and refill with fresh water and a suitable
inhibitor.
▶ Vent any air from the boiler and system.
Danesmoor Kitchen and Kitchen System 6 720 808218 (2013/10)
INHIBITOR
Add a suitable inhibitor or combined inhibitor/anti-freeze, if the system
is exposed to freezing conditions, to the heating system in accordance
with the DWTA code of practice and manufacturer's guidelines.
WARNING: Sealing agents
▶ In cases where all attempts to find a system micro
leak have failed, Worcester, Bosch Group supports
the use of Fernox F4 leak sealer.
Water treatment
Suitable water treatment products can be obtain from the following
manufacturers:
FERNOX
0870 601 5000
www.fernox.com
SENTINEL
0800 389 4670
www.sentinel-solutions.net
ARTIFICIALLY SOFTENED WATER
It is possible to have an ion exchange water softener fitted to the cold
water system of the property. However, the boiler requires an untreated
cold water connection taken from the mains supply, before the water
softener, to the primary water filling point of the heating system.
Alternatively there are water softening/treatment devices that do not
adjust or alter the pH levels of the water. With these devices it may not
be necessary to provide an untreated water by-pass to the primary water
filling point of the heat system.
NOTICE: ARTIFICALLY SOFTENED WATER MUST NOT
BE USED TO FILL THE CENTRAL HEATING SYSTEM.
4.2

Mains supply

4.2.1

Electrical supply

• Supply: 230V - 50 Hz
• Cable: PVC insulated 0.75 mm2 (24 x 0.2mm) temperature rated to
90°C.
• External 5A fuse to BS1362.
• The appliance must be earthed.
• This appliance must not be connected to a three phase supply.
• IP20
• Wiring must comply with the latest IEE wiring regulations.
• It must be possible to isolate the appliance from the electrical supply
with at least a 3mm contact separation in both poles supplying the
appliance.
• Wiring between the appliance and the electrical supply must comply
with IEE wiring regulations and any local regulations that may apply
for fixed wiring to a stationary appliance.
• Any system connected to the boiler must not have a separate
electrical supply.