4. REFRIGERANT FLOW DIAGRAM

Indoor Unit
SAP – K71GJA
SAP – K91GJA
SAP – K121GJA
Indoor Unit
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
CAUTION
Outdoor Unit
Wide tube
O.D.
ø9.52 mm
(3/8 ")
or
O.D.
ø12.7 mm
(1/2 ")
Narrow tube
O.D.
ø6.35 mm
(1/4")
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
SAP – C71GA
SAP – C91GA
SAP – C121GA
Outdoor Unit
Wide tube
service
Muffler
valve
Narrow
tube
service
valve
Capillary tube
Thickness:
Min. 8 mm
19
SAP – C91JA
SAP – C121JA
Compressor
Accumulator
Insulation
Wide tube
Thickness:
Min. 8 mm
Narrow tube