Honeywell C7061A1020 Manual page 15

Dynamic self check ultraviolet flame detector
Hide thumbs Also See for C7061A1020:
Table of Contents

Advertisement

Fig. 13. Replacing coil and shutter assembly.
Replacing the Quartz Viewing Window (or
Focusing Lens) C7061A Only
IMPORTANT
A quartz window or lens must be used. Ordinary
glass absorbs or filters out ultraviolet radiation.
A Open the master switch; remove the detector from the
sight pipe and remove the detector cover. (see
appropriate sections.)
B Remove the ultraviolet sensing tube (steps A through E
of Replacing the Ultraviolet Sensing Tube section).
C Loosen the three screws holding the back section of the
mounting flange to the faceplate. Carefully remove and
keep together the three screws, the gray fiber-
neoprene gasket, the red rubber washer, and the back
section of the mounting flange.
NOTE: if the viewing window (with its rubber mounting
gaskets) is stuck to the mounting flange skip step D.
IMPORTANT
Be very careful not to kink or otherwise damage
the flexible shutter.
D Using the eraser end of a pencil, push out the viewing
window (with its rubber mounting gaskets) from the inside
of the faceplate.
E Insert one rubber mounting gasket into the window
aperture in the faceplate.
F Insert the new quartz viewing window (or focusing lens).
G Insert two rubber mounting gaskets (only one gasket
when replacing a focusing lens) into the aperture.
H Put the back section of the mounting flange, rubber
washer, and fiber-neoprene gasket in place on the
faceplate, and securely tighten the three mounting
screws.
NOTE: Make sure the red rubber washer between the gray
fiber-neoprene gasket and the back section of the
mounting flange does not protrude over the window
aperture or otherwise obscure the detector line-of-
sight.
บริ ษ ั ท เอดี ด ี เฟอร์ เ นส จํ า กั ด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258
https://www.add-furnace.com E-mail: sales@add-furnace.com
Fig. 14. Replacing quartz viewing window or focusing lens
I Clean the viewing window (or focusing lens) on both
J Reinstall the sensing tube (steps F through I of
K Replace the detector cover and reinstall the detector on
Replacing Focusing Lens C7061F Only
A Remove the detector from the sight pipe (see Fig. 15).
B Remove the 3 screws from the threaded flange (pipe
C Replace the lens and tighten the 3 screws.
Fig. 15. Replacing focusing lens on C7061F1003
15
sides using a clean cloth placed over the eraser end of a
pencil.
Replacing the Ultraviolet Sensing Tube section).
the sight pipe.
IMPORTANT
A quartz window or lens must be used. Ordinary
glass absorbs or filters out ultraviolet radiation.
connection) which houses the 124204 Focusing Lens.
EN1C-0015 R2105

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F1003C7061f1003

Table of Contents