Installing The Airflow Vent Nxa-Acc-Bav4 - Cisco Nexus 93360YC-FX2 Hardware Installation Manual

Aci-mode switch
Hide thumbs Also See for Nexus 93360YC-FX2:
Table of Contents

Advertisement

Installing the Chassis
1
Slide the power-supply end of the chassis onto the
bottom-support rails so that the chassis locks onto the
chassis stops at the end of the rails.
2
Chassis stops for holding the chassis (positioned by
the aisle required for the fan and power supply
modules).
Step 2
Use a customer-supplied rack-mount screw (an M6 x 10 mm screw or other appropriate screw for the rack) to attach each
of the two mounting brackets on the chassis to the rack and tighten each screw to the appropriate torque setting for the
screw (for M6 x 10 mm screws, use 40 in-lbs [4.5 N·m] of torque).

Installing the Airflow Vent NXA-ACC-BAV4

The airflow vent bracket (NXA-ACC-BAV4) is required for NEBS (Network Equipment-Building System)
compliance.
3
Receiving hole on each side of the chassis for the
chassis stops on the bottom-support rails.
4
Customer-supplied rack-mount screw (M6 x 10 mm
screw or other screw appropriate for the rack) used to
secure each side of the chassis to the rack.
Cisco Nexus 93360YC-FX2 ACI-Mode Switch Hardware Installation Guide

Installing the Airflow Vent NXA-ACC-BAV4

23