Honeywell SILENT KNIGHT 5895XL Manual page 11

Intelligent power module
Hide thumbs Also See for SILENT KNIGHT 5895XL:
Table of Contents

Advertisement

5895XL Board and Terminal Strip Description
Terminal # and Label
1
L
2
G
3
N
4
X
5
O
6
X
7
O
8
X
9
O
10
X
11
O
12
X
13
O
14
X
15
O
16
B
17
A
18
+
19
-
20
B
21
A
22
+
23
-
24
N.C.
25
C
26
N.O.
27
N.C.
28
C
29
N.O.
30
B
31
A
32
+
33
-
1
Regulated/special application when used for releasing
5895XL Manual — P/N 151142-L8:M 2/15/2022
Description
AC input (hot)
Earth ground
AC input (neutral)
1
I/O 6
Flexput Circuit
I/O 5*
Flexput Circuit
I/O 4*
Flexput Circuit
I/O 3*
Flexput Circuit
I/O 2*
Flexput Circuit
I/O 1*
Flexput Circuit
SBUS OUT
SBUS communication
SBUS power
SBUS IN
Used for Class A installations
RELAY 2
General Purpose Relay 2
RELAY 1
General Purpose Relay 1
SBUS IN/
5895XL communication with main
OUT
panel or to controlling 5895XL if
daisy-chained
MAIN
5895XL SBUS power (from FACP) 24 VDC
Table 2.1 Terminal Strip Description and Electrical Ratings
Rating
Voltage
120 VAC,50/60 Hz
2.7 A
N/A
N/A
120 VAC,50/60 Hz
2.7 A
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA
Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
5 VDC
100 mA
24 VDC
1.0 A
24 VDC
2.5 A
24 VDC
2.5 A
5 VDC
100 mA
10 mA
Before You Begin Installing
Current
11

Advertisement

Table of Contents
loading

Table of Contents