Honeywell MI-DCZME Installation Instructions

Honeywell MI-DCZME Installation Instructions

Advertisement

Available languages

Available languages

Quick Links

Fig./Abb. 1
1:2 DIN
1:1 M200E-SMB
Sollevare
Levantar
Anheben
Fig./Abb. 2
Fig./Abb. 3
Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ
M200-504-00
60°C
-20°C
2
1
Rotate
Plug
Ruotare
Inserire
Girar
Conectar
Drehen
Einhaken
Clip / Agganciare
3
Acoplar / Einrasten
3
1
Lift
Push down
Premere
Precionar
hacia abajo
Runterdrücken
2
Rotate / Ruotare
Girar / Drehen
MI-DCZME
0905 22
0905 22
DOP-IOD102
EN 54-17: 2005, EN 54-18: 2005
Honeywell Morley-IAS
Pittway Tecnologica S.r.l
Via Caboto 19/3
34147 Trieste, Italy
MI-DCZME
EN
CONVENTIONAL ZONE INTERFACE MODULE
This manual is intended as a quick reference installation guide. Please refer to the
control panel manufacturers installation manual for detailed system information.
The Morley series of modules are a family of microprocessor controlled interface
devices permitting the monitoring and/or control of auxiliary devices.The MI-DCZME
MI-DCZME
provides an interface between a zone of System Sensor manufactured conventional
type fire detection devices and an intelligent signalling loop.
A single tri-colour LED indicates the status of the module. In normal conditions, the
LED can be set by command from the control panel to blink green when the module
is polled. In the case of a fire alarm on the conventional zone, the LED is switched
on constant red by panel command. If a fault is detected on the conventional zone or
the zone supply voltage drops below 18V, or a fault with the external power supply is
M200E-SMB
signalled, the LED will blink yellow if enabled on the control panel. When a short circuit
is detected on the loop to either side of the module, the LED is switched to show a
constant yellow light.
This module does not require maintenance.
SPECIFICATIONS
Intelligent Loop
Operating Voltage Range: see S00-7100
LED Cutoff Voltage: 16.5VDC
Max. Standby Current (µA @24 V and 25
No Communication:
Max. Standby Current (mA @24 V and 25
Capacitive EOL only, Loop Powered Conventional Zone:
No Communication:
LED Current (Red):
LED Current (Yellow):
Isolator Features: see S00-7100
Conventional Zone
Supply Voltage:
Maximum Standby Load Current: 3mA for detectors
Maximum Zone Load:
Maximum Conventional Line Resistance: 50 Ohm (both legs)
End of Line Capacitor:
General
Humidity:
Ingress protection:
Maximum Wire Gauge:
INSTALLATION
Note: These modules must only be connected to control panels using compatible
proprietary analogue addressable communication protocols for monitoring and control.
Morley series modules can be mounted in several ways (See Figure 1):
1:1 An M200E-SMB custom low profile surface-mounting box. The SMB Base is
affixed to mounting surface, and then the module and cover are screwed onto
the base using the two screws supplied. Box dimensions: 132mm(H) x 137mm(W)
x 40mm(D)
1:2 The DIN bracket on top allows mounting onto standard 35mm x 7.5mm "Top Hat"
DIN rail inside a control panel or other suitable enclosure. Install and remove as
shown in Figure 1:2
Wiring to all series Morley modules is via plug in type terminals capable of supporting
conductors up to 2.5mm²
Disconnect loop power before installing modules or sensors.
The module address is selected by means of rotary decade address switches (see
Figure 3). A screwdriver should be used to rotate the wheels to select the desired
address, either from the front or the top of the module.
Note: The number of addresses available will be dependent on panel capability,
check the panel documentation for information on this.
Short Circuit Isolators
All Morley series modules are provided with short circuit monitoring and isolators on
the intelligent loop. If required the isolators may be wired out of the loop to facilitate
the use of the modules on high current loaded loops, for example if sounders are
used. To achieve this, the loop out positive should be wired to terminal 5 rather than
terminal 2. See Figure 2 for details.
INSTALLATION INSTRUCTIONS - MI-DCZME
C) External Supply Conventional Zone:
o
C) Conventional Zone connected to
o
1.3mA
4.5mA
18 to 32 VDC (either from loop or external supply)
17.5mA (Limited internally)
47μF non-polarised. M200E-EOL-C supplied
5% to 95% relative humidity (non-condensing)
IP44 (Mounted in M200E-SMB)
2.5mm²
CAUTION
CAUTION
Electrostatic Sensitive Device
Observe precautions when handling and making connections
120
1.3
I56-4423-000

Advertisement

loading

Summary of Contents for Honeywell MI-DCZME

  • Page 1 EN 54-17: 2005, EN 54-18: 2005 CAUTION Electrostatic Sensitive Device Honeywell Morley-IAS Observe precautions when handling and making connections Pittway Tecnologica S.r.l Via Caboto 19/3 34147 Trieste, Italy Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ M200-504-00 I56-4423-000...
  • Page 2 MI-DCZME Wiring INSTALLAZIONE The MI-DCZME can be wired so as to power the conventional zone either from an Nota: Questi moduli possono essere collegati esclusivamente a pannelli di controllo external supply, or directly from the communications loop provided it can supply dotati di opportuno protocollo di comunicazione proprietario, indirizzabile ed analogico, sufficient current.
  • Page 3 Conexiones MI-DCZME MONITOR PARA ZONAS CONVENCIONALES MI-DCZME El MI-DCZME se puede conectar para que la zona convencional se alimente externamente o directamente del lazo de comunicaciones si éste puede suministrar la suficiente corriente. Si se utiliza una fuente de alimentación externa, la zona Este manual ha sido preparado para que sirva como guía de referencia rápida en la...
  • Page 4 MI-DCZME Anschaltung Das Modul MI-DCZME kann so angeschaltet werden, dass die Standardmeldergruppe INSTALLATIONSANLEITUNG FÜR MI-DCZME von einem externen Netzteil oder, vorausgesetzt der Strombedarf kann gedeckt INTERFACE-MODUL FÜR werden, direkt von der Ringleitung versorgt werden kann. Beim Einsatz einer externen STANDARDMELDERGRUPPEN Spannungsversorgung ist die Standardmeldergruppe vollständig von der Ringleitung...