Honeywell Notifier NZM-100-6 Installation And Maintenance Instructions Manual page 4

Six zone interface module

Advertisement

FIGURE 8. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B
CONNECT MODULES TO
LISTED COMPATIBLE
FIRE•LITE CONTROL
PANELS ONLY
3.9K EOL
RESISTOR
(INCLUDED)
+
CLASS B IDC (TYPICAL)
TO PANEL CONTROLLED
RESETTABLE POWER SUPPLY
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT DEVICE
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
1. To use a common power supply between multiple NZM-100-6
modules, connect a long power supply jumper from T5 or T6
to T5 or T6 on the adjacent NZM-100-6 module.
FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A
CONNECT MODULES TO LISTED COMPATIBLE
FIRE•LITE CONTROL PANELS ONLY
+
+
CLASS A IDC (TYPICAL)
TO PANEL CONTROLLED
RESETTABLE POWER SUPPLY
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT DEVICE
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
1.
To select Class A, remove the two shunts from the "A/B select" positions.
2.
To use a common power supply between multiple NZM-100-6 modules,
connect a long power supply jumper from T5 or T6 to T5 or T6 on the
adjacent NZM-100-6 module.
+
(+)
(–)
POWER-LIMITED
AND SUPERVISED
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
IDC 2
IDC 3
(+)
(–)
POWER-LIMITED
AND SUPERVISED
Detectors must be UL listed compatible with the module. Install detectors per
manufacturers installation instructions.
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
4
3
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
4
BASE ADDRESS
6 7 8 9
6 7 8 9
5
5
10
4
4
11
3
3
12
2
13
2
1
1
14
0
0
15
BASE ADDRESS
6 7 8 9
6 7 8 9
5
5
10
4
11
3
12
2
13
2
1
1
14
0
0
15
STATUS
INDICATORS
C0779-04
STATUS
INDICATORS
C0780-03
I56-2990-004
7/1/2022