Mitsubishi Electric CAHV-R450YA-HPB Installation & Operation Manual page 36

Hot water heat pump unit
Hide thumbs Also See for CAHV-R450YA-HPB:
Table of Contents

Advertisement

(5) Setting the total number of units for a multiple system
Step 0
Set the ON/OFF
switch (SWS1) to
OFF.
Step 1
Set the dip switches
SW5 and SW6.
Step 2
Select the desired
item with the push
switch SWP3.
Step 3
Press the push
switches SWP1 (↑)
or SWP2 (↓) to
increase or
decrease the value.
Step 4
Press the push
switch SWP3 to
save the change.
Step 5
Turn the power back
on.
Reset the system.
Setting the unit addresses
Refer to
"System configuration procedures: Multiple system" (page 23)
Set SWS1 to OFF from the remote controller or with the local switch.
Settings cannot be changed unless the ON/OFF switch is set to OFF.
Set the dip switches on the circuit board as follows to select how external inputs are received.
SW5
10
5
6
7
OFF
OFF
OFF
OFF
The item codes shown in the table below will appear in order every time the push switch
SWP3 is pressed.
Use the push switches SWP1 and SWP2 to change the value of the selected item.
The value will keep blinking while it is being changed.
Setting the total number of units
Total number of units in the system*1
*1 Enter the total number of units including the main unit. Applicable only to the main unit.
Press SWP3 once within one minute of changing the setting with SWP1 or SWP2 to save the
setting.
Once the new setting is saved, the display will stop blinking and stay lit. The display will, then,
return to the item code display mode.
If SWP3 is not pressed within one minute, the change will not be saved and the display will
return to the item code display mode.
After changing the settings, re-initialize the system according to the procedures detailed on
page 27.
Note
The new setting will not be saved unless a reset is performed.
SW6
8
9
10
ON
ON
ON
Item code
Increments
107
1
.
36
Lower limit
Upper limit
1
16
Initial value
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CAHV-R450YA-HPB and is the answer not in the manual?

Questions and answers

Rod Hewitt
February 3, 2025

How best to layout 6no CAHV- 450 units

1 comments:
Mr. Anderson
February 10, 2025

The best layout for six Mitsubishi Electric CAHV-R450YA-HPB units should follow these guidelines:

1. Spacing Requirements:
- Maintain a minimum clearance of 500 mm in front of each unit.
- Maintain a minimum clearance of 300 mm between adjacent units.

2. Foundation and Fixing:
- Install units on a concrete or iron foundation.
- Securely fix each unit with bolts to prevent movement due to earthquakes or strong winds.
- Ensure the foundation supports the unit’s legs completely.

3. Noise and Vibration Control:
- Use rubber vibration isolators large enough to cover the unit’s leg width.
- Avoid direct transmission of noise and vibrations to walls and floors.

4. Arrangement:
- Arrange the six units in a group within a 6-meter area, ensuring proper spacing.
- Ensure sufficient airflow around each unit to maintain efficiency.

Following these guidelines ensures proper operation, safety, and efficiency of the six heat pump units.

This answer is automatically generated

This manual is also suitable for:

Cahv-r450ya-hpb-bs

Table of Contents

Save PDF