Bosch Rexroth ctrlX I/O XI312204 Manual

Bosch Rexroth ctrlX I/O XI312204 Manual

Analog input terminal

Advertisement

Quick Links

ctrlX I/O
Analog Input Terminal
4-channel, 0 to 10 V, 16 Bit, Bipolar
DOK-XIO***-XI312204*AI-DA01-EN-P
1
XI312204
The analog input terminal XI312204 processes signals in the
range from 0 to 10 V in a ctrlX I/O station. The input signal
is digitized with a resolution of 16 bits and transferred galvan-
ically isolated to the system level. The 4 input channels are
differential inputs. Error states are shown at the channel LED
on the removable peripheral connector and routed to the con-
trol via the local bus.
The logic and peripheral voltage supply as well as the
EtherCAT-based module communication are routed through
the module.
For the integration into the parent system, the respective ESI
files are available. For the ESI files, go to ⮫ http://www.bos-
chrexroth.com/electrics.
Ensure
that
the
current
For the current documentations, go to ⮫ www.boschrex-
roth.com/mediadirectory.
Fig. 1: Module XI312204
2
Ordering data
Type
Part number Description
XI312204
R911406105 Analog input module, voltage
For more ordering data (accessories), go to the product cat-
alog under ⮫ www.boschrexroth.com/electrics.
3
Technical data
3.1 General technical data
XI312204
Number of inputs
4
Connection method Push-in
documentation
is
consulted.
between 0 and 10 V
XI312204
Connection method 2-wire, shielded, twisted in pairs
Signal type
Differential
Input signal
0 V to 10 V
Input resistance
>250 kΩ
Limit frequency of
12.8 kHz
input filter
100 μs
Conversion time
Resolution D/A
16 bits incl. sign
Typ. ± 0.1 % of the end value of the
Accuracy
measured range (MBE)
Max. ± 0.3% of MBE
Overload protection No, DC 30 V max.
Max. ±35 V compared to U
Common Mode
Voltage supply
U
P
Current consumption
40 mA
U
L
Current consumption
21 mA
U
P
Bit width, input data
18 bytes in the standard representation
in the process data
12 bytes in the "compact" representa-
image
tion
(including filling bit)
Can be set channel-granularly
Parameterization
Via ctrlX Works (start parameter)
Configuration
No address or configuration setting
required
Dimensions
12 mm × 105 mm × 99 mm (width ×
height × depth)
Weight
95 g (module including connector)
Electrical isolation
DC 1200 V U
FE
EMC resistance
Acc. to EN 61000-6-2 and EN 61000-6-4
Mounting position
Vertical, on a horizontal support rail
Labeling, approvals
CE, UKCA
3.2 Clamping point assignment
Clamping
Signal
point
1
AI Kanal 1+
2
AI Kanal 1-
3
AI Kanal 2+
4
AI Kanal 2-
5
AI Kanal 3+
6
AI Kanal 3-
7
AI Kanal 4+
8
AI Kanal 4-
R911418823
Edition 01
GND
P
via jumper contacts
to U
, DC 707 V U
P
L
LED
Pusher
Red
Grey
None
Grey
Red
Grey
None
Grey
Red
Grey
None
Grey
Red
Grey
None
Grey
R911418823, Edition 01, 1 / 8
/U
to
P
L

Advertisement

Table of Contents
loading

Summary of Contents for Bosch Rexroth ctrlX I/O XI312204

  • Page 1 ctrlX I/O Analog Input Terminal 4-channel, 0 to 10 V, 16 Bit, Bipolar R911418823 DOK-XIO***-XI312204*AI-DA01-EN-P Edition 01 XI312204 XI312204 Connection method 2-wire, shielded, twisted in pairs The analog input terminal XI312204 processes signals in the Signal type Differential range from 0 to 10 V in a ctrlX I/O station. The input signal is digitized with a resolution of 16 bits and transferred galvan- Input signal 0 V to 10 V...
  • Page 2: For Your Safety

    3.3 Internal schematic diagram 11 ms semi-sinusoidal 15 g Broadband noise 20-500 Hz with 1.22 g RMS, Acc. to DIN EN 60068-2-64 30 min in all three axes System bus µC AI_1 For the current approvals, go to AI_4 ⮫ www.boschrexroth.com/electrics. 24 V DC/DC For your safety...
  • Page 3 Note that the input value range of the module from 0 V up to Enter the value "User_gain" into the parameter "80x0:01 User reaching the upper limit value is specified at 108% of the end gain". value of the measured range (MBE). Normally, higher values = (Scaled_Lower_Range_End_Value) −...
  • Page 4: Object Directory

    5.7 Limit 1/2 Threshold Check Index Object Data type Direc- Error, Diagnostic Unit (hex) name tion warning, number, There are two individual and independent limit value checks informa- description per channel specifying whether the process data value is tion lower, equal to or higher than the limit value set. ‒...
  • Page 5 Process data consists of the value and the diagnostic data in Word 1 Channel 1 Value the standard representation: Word 2 Channel 2 Value Word 1 Channel 1 Value Word 3 Channel 3 Value Word 2 Word 4 Channel 4 Value Byte 1 Word 5 Bit 0...
  • Page 6: Status Codes

    Installation 8.2 Diagnosis history 10F3 The object 10F3hex is implemented as ring memory into the 9.1 Connection instructions "Overwrite mode". The latest 20 diagnostic messages are Differential input and potential reference stored. Older messages are deleted. The following table shows the structure of a diagnostic mes- For analog inputs, there are differential inputs without a refer- sage of the bus coupler for EtherCAT.
  • Page 7: Installation Notes

    – Additionally, provide sufficient distance for mounting, dis- mounting, plugs and cables. 24 V – If more devices are connected in series to the station on the left or right, the surface temperature may not exceed 60° C Input – In case of a several line design, the supply air has to be Input measured under each line and its limit value may not be...