1. Combination Table: Indoor units
Model
1.5
1.7
HSP Duct
OAP Duct
Big Duct
Hydro
Unit HE
Hydro
Unit HT
ERV Plus
NOTE
• Make sure to use an indoor unit that is compatible with DVM S.
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
❇ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
❇
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
❇ Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
❇
2.2
2.8
3.2
3.6
Capacity (kW)
4.5
5.6
6.0
7.1
8.2
9.0
11.2
12.8 14.0 16.0
11