Download Print this page

Honeywell PEHA 960/3 PSB/D Installation And Operating Instruction page 3

Phc dimming system box

Advertisement

Available languages

Available languages

PEHA Elektro GmbH & Co. KG
Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: peha@peha.de • Internet: www.peha.de
InsTALLATIOn AnD OPerATIng InsTrucTIOn
Phc dimming system box
960/3 PsB/D
DescrIPTIOn
The PHC dimming box has 8 inputs (Input 8-15) that can be switched against ground
Vorsicht! Kontamination
Vorsicht! Kontamination
(0V) using push buttons. The inputs can be used to control the outputs of the PHC output
modules or of the PHC system boxes. The 4 outputs (Out 0-3) of the PHC dimming
box are used to switch and dimm dimmable electronic ballasts with 1-10V input. They
are supplied by a 3 pole through line carrying with a voltage of 230 V~/50-60 Hz.
notes:
– Detailed expert knowledge for programming a PHC system
Vorsicht, Gefahr durch
Vorsicht, Gefahr durch
are required.
elektrischen Strom
elektrischen Strom
– The PHC-functions for the PHC system are to be programmed
with the PHC system software (see PHC manual).
– Read through the operating instructions carefully before putting
the device into service.
Vorsicht, Gefahr durch
Vorsicht, Gefahr durch
heiße Oberfläche
Laserstrahlung
sAFeTy
cAuTIOn! Danger of electrical shock!
The housing contains current-carrying components. contact can lead
to personal injury! All work on the mains network and the device may
only be done by an authorised electrician.
Vorsicht, Warnung vor
Vorsichtig verschieben!
einer Gefahrstelle
- veraltet -
• Disconnect power supply from the device prior to performing any work on it.
• Secure the device against being powered on again.
• Check that the device is powered off.
• Close the housing securely before applying power.
The following must be observed:
• Prevailing statutes, standards and regulations.
Wandhydrant (2.
Wandhydrant, mit Angabe
Vorschlag)
des Anschlusses
• State-of-the-art technology at the time of installation.
• The PHC manual and operating instructions of the PHC modules.
• Operating instructions can only cite general stipulations. These are to
be viewed in the context of a specific system.
The following systems may not be switched:
• Safety switches such as EMERGENCY OFF
• Emergency power supplies
• Fire alarm systems
• Emergency lighting systems
This device is only intended to be used for its stated application. Unauthorised
conversions, modifications or changes are not permissible!
This device may not be used in conjunction with other devices whose operation could
present a hazard to persons, animals or property.
TechnIcAL sPecIFIcATIOns
general data
Power supply
Maximal load of
the system box
Own consumption
relay service life
Power line protection
coding
Ambient temperature
storage temperature
connections
Test specifications
certifications
Protection type
Dimensions
Load specifications per output (Out 0-3)
electronic ballast
note: To calculate the current consumption for the power supply, you should assume
a consumption of 60 mA. The power consumption increases to 150 mA for about 1
s when switching on the relays.
PEHA_M_960-3_ PSB-D (Rev05_130320)
Vorsicht, Gefahr durch
Vorsicht, Gefahr durch
Abquetschen
Abschneiden
Vorsicht, Gefahr durch
Vorsicht, Gefahr durch
elektromagnetische
explosionsgefährliche
Strahlung
Stoffe
Vorsicht, Gefahr durch
Vorsicht, Gefahr durch
Radioaktivität
Rutschen
Während der
Wandbrände nicht von
Schweißarbeiten,
oben löschen
Arbeitsstelle beobachten
Wareneingang -
Wareneingang - Gesperrt
Freigegeben
230 VAC /50-60 Hz (L, N, PE)
4000 W (250 VAC / 16 A)
10-60 mA
ca. 40.000 applications at max. load
Circuit breaker (max. 16 A)
8 pole dip switch for module address
0 to + 50 °C
– 40 to + 85 °C
8 Push button inputs (INPUT 8-15)
3 switches max. allowed!
1 PHC bus input (BUS-IN)
4 Outputs (OUT 0-4)
2 PHC bus output (BUS-OUT)
EN 60669-2-1
CE ; KEMA/KEUR
IP20
L 180 mm x W 205 mm x H 48 mm
5 items
GB
InsTALLATIOn
Installation and commissioning may only be done by an authorised electrician. Mains
power to electrical equipment must be switched off during installation. Applicable
laws and standards of the country in which the device is operated must be observed!
The PHC dimming box can be mounted in any location using the included screws and
plugs (e.g. onto a smooth wall or inserted ceiling ). The base of the PHC dimming box
is used as a template for the drill holes.
Vorsicht, Gefahr durch
Abstürzen
• Carry out installation and switch on electrical system (supply line).
• The input and output functions of the PHC switching box have to be programmed
in the PHC software (see PHC manual).
• Carry out program transfer with PHC software.
Vorsicht, Gefahr durch
DATA cOnnecTIOn
feuergefährliche Stoffe
Usually, a JY(ST)Y 2x 2x 0,8 mm Ø cable is used as a data line. The cable is connected
to the 4 pole connectors (included). The data connection to the PHC switching box
is carried out at the „BUS-IN" input. A data connection for further PHC system boxes
or PHC modules is carried out at the „BUS-OUT" output.
notes:
Vorsicht, Gefahr durch
– Switch off power supply before connecting or disconnecting bus line.
Stolpern
– The module can be positioned anywhere in the data line.
– The module is supplied with voltage by the bus line.
cODIng sWITch
The coding switch sets the module address. The setting is presented in the
Wandbrände von unten
PHC software under menu item „Components  Modules".
nach oben löschen
notes:
– Do not set the same module addresses for PHC switching boxes.
– Before setting the module address, the PHC module needs to be
switched off and it must be secured against electrical discharge.
Wärmeabzugseinrichtung
Turn-On cOnDITIOns
You can select the switching states of the outputs (OFF, Memory and ON) on voltage
switch-on or recovery in the PHC software under the menu item „Components 
Turn-on conditions":
The turn-on conditions are pre-set to „OFF". The „Memory" switching condition is
selected, e.g. , to get the previous switching state for the switching box from the control
module after a voltage interruption (> 50 ms).
TrOuBLeshOOTIng & reMeDIes (eLecTrIcIAn OnLy)
new system or existing system
• Check circuit breaker and power supply
• Check connected electrical loads and connection cables
• Check module address (coding switch).
• Check PHC programming and transfer again (see PHC manual).
contact
Telephone: ...................+49 (0)2351 185-0
Fax:..............................+49 (0)2351 27666
Internet: .......................www.peha.de
E-mail: .........................peha@peha.de
WArrAnTy cOnDITIOns
These operating instructions are an integral part of both the device and our terms of
warranty. They must be handed over to the user. The technical design of the appliance
is subject to change without prior notification. PEHA products are manufactured
and quality-checked with the latest technology according to applicable national and
international regulations. Nevertheless, if a product should exhibit a defect, PEHA
warrants to make remedy as follows (regardless of any claims against the dealer to
which the end user may be entitled as a result of the sales transaction):
In the event of a justified and properly established claim, PEHA shall exercise its
prerogative to either repair or replace the defective device. Further claims or liability
for consequential damage are explicitly excluded. A justifiable deficiency is deemed to
exist if the device exhibits a structural, manufacturing, or material defect that makes it
unusable or substantially impairs its utility at the time it is turned over to the end user.
The warranty does not apply to natural wear, improper usage, incorrect connection,
device tampering or the effects of external influences. The warranty period is 24 months
from the date of purchase by the end user from a dealer and ends not later than 36
months after the device's date of manufacture. German law shall be applicable for the
settlement of warranty claims.
DIsPOsAL OF The DeVIce
Do not dispose of old devices in the household waste! The device must be
disposed of in compliance with the laws and standards of the country in which it
is operated! The device contains electrical components that must be disposed of
as electronics waste. The enclosure is made from recyclable plastic.