4.2 Digital Output Telegram

To write the digital output telegram, use Modbus function code 5 Write Single Coil or 15 (0Fh)
Force Multiple Coils. To read the digital output telegram, use Modbus function code 1 Read Coil
Status or 2 Read Input Status.
Address for data access to device connected to port
1
2
1800h
1810h
1801h
1811h
1802h
1812h
1803h
1813h
1804h
1814h
1805h
1815h
1806h
1816h
1807h
1817h
1808h
1818h
1809h
1819h
180Ah
181Ah
180Bh
181Bh
180Ch
181Ch
180Dh
181Dh
1SFC132374M0201
3
4
1820h
1830h
1821h
1831h
1822h
1832h
1823h
1833h
1824h
1834h
1825h
1835h
1826h
1836h
1827h
1837h
1828h
1838h
1829h
1839h
182Ah
183Ah
182Bh
183Bh
182Ch
183Ch
182Dh
183Dh
16
Data
Description
Reserved
Stop
Commence a stop when
this coil is set (this coil has
higher priority than the
start coil). The stop coil is
only acknowledged if the
Auto mode coil is set.
Start
Commence a start when
this coil is set. The start
coil is only acknowledged
if the Auto mode coil is
set.
Reserved
Reserved
Auto mode
This coil must be set for
controlling the motor.
Fault reset
Reset an active fault or
protection when this coil is
set.
Reserved
Reserved
Reserved
Reserved
Reserved
Clear active
Clear active diagnostics
diagnostics
when this coil is set
Reserved