88 and 175 lb-in (10 and 20 nm) spring return direct coupled actuators

Advertisement

MSXX10, MSXX20 SERIES
85°
S1
S2 S3
S4
S5
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
Fig. 12. Terminal block details.
Terminal
Floating
1
power
2
common
3
cw
4
ccw
5
feedback
a
Only applies to models with wires.
Typical Wiring Without Cables
1
24 VAC
2
NOTES: AFTER TRANSFORMER SELV–SAFETY EXTRA LOW VOLTAGE FOR
INTERNAL CIRCUIT AND MOTOR.
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
Fig. 13. Wiring for low-voltage two-position control.
63-2607—26
ACTUATOR
2
OR
OR
V
N/A
+
S6
4
5
1
2
3
1
M33486
Table 6. Wiring details.
Modulating
power
common
input
feedback
1
SPST
V
3
2
ACTUATOR
M35094
Two-Position
120 Vac
24 Vac
240 Vac
power
power
common
neutral
1
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
Fig. 14. Wiring for line-voltage two-position control.
10
Sylk-enabled
Color
power
Red
common
Black
s-bus
White
s-bus
Brown
1
SPST
2
2
ACTUATOR
a
V
M22289A