Parameter Overview And Data Entry In "Condense Form - ABB COPA-XT DT43F Instruction Bulletin

Electromagnetic flowmeter in 2-wire technology with pulsed dc magnetic fields
Table of Contents

Advertisement

5.4.
Parameter Overview and Data Entry in "Condensed Form"
Submenu/Parameter
* Prog. Protection *
on
Prog. Prot. Code
Language
English
Meter Size
DN 50
2 In
Q
10 m/s
max DN
60.00
m3/h
Qmax
12.000
m3/h
Pulse
1.0000
/m3
Pulse Width
30.000 ms
Entry Type
from table/numeric
* Prog. Protection *
ENTER
off
PP-Code?
0
* Prog. Protection *
off
numeric
Old PP-Code?
ENTER
0
New PP-Code?
0
from table
numeric
Electromagnetic Flowmeter COPA-XT
Data can only be entered after the program protection has been
turned off.
on/off
If a PP-Code other than "0" (factory setting) has been stored, then
the program protection can only turned off after the appropriate
PP-Code (1-255) has been entered.
program protection is turned off, parameters can be
When the
changed.
program protection is turned off, it is possible to enter a
When the
new PP-Code.
Enter old PP-Code
0 = factory setting
Enter new PP-Code (0-255)
English, German
The meter size of the flowmeter
See Instrument Tag
Automatic flow range end value setting determined form the meter
size selection
Flow range end value can be set from
0.05 Q
to 1 Q
max DN
Flow range for forward and reverse flow directions
Min. flow range setting 0 - 0.5 m/s
Max. flow range setting 0 - 10 m/s
Flow range end value can be set between 0.5 and 10 m/s
For int. and ext. flow totalization, range 0.001 - 1000 pulses
per selected units, max. count Frequency 100 Hz.
For external pulse output,
Range 0.1 ms - 2000 ms
Comments
max DN
17