4.4.16 Frequency Trigger
Brief description
The output is switched on or off depending on whether the
frequency at the input is between two definable limits.
Symbol in
LOGO!
Timing diagram
Q
G_T
fre
LOGO! Manual
A5E00067781 01
Connection
Input Cnt
Parameter Par:
SW , SW
G_T
Output Q
fa = 6
fa = 10
Description
At the Cnt input you apply
the input that supplies the
pulses to be counted.
Use
Inputs I5/I6 or I11/I12
(LOGO!...L) for rapid
counts (not
LOGO!230..., 24RC,
24RCo):
max. 1 kHz.
Any other input or circuit
component for lower fre-
quencies.
SW : on threshold
SW : off threshold
G_T: time period over which
the signal pulses applied
are counted.
Q switches on or off de-
pending on SW and SW .
fa = 8
fa = 5
LOGO! Functions
SW = 9
SW = 5
113