ACVATIX™
2-port shutoff valves and 3-port changeover ball valves, PN 40,
with internally threaded connection
VAI60.., VBI60..L, VBI60..T
CE1N4213en
2020-02-20
VAI60..
For use in heating, ventilation, and air conditioning plants as shutoff or change-
over ball valve. In closed circuits.
Ball valve body made of brass, UNS C35330 (DZR)
DN 15...50
5...96 m
3
k
/h
vs
Connections with internal threading Rp per ISO 7-1
Rotational angle 90°
Can be used with electromotorized rotary actuators GQD..9A, GMA..9E with
spring return and GSD..9A, GDB..9E, GLB..9E without spring return
VBI60..L
VBI60..T
Smart Infrastructure

Advertisement

loading

Summary of Contents for Siemens ACVATIX VBI60.15-5L

  • Page 1 ACVATIX™ 2-port shutoff valves and 3-port changeover ball valves, PN 40, with internally threaded connection VAI60.., VBI60..L, VBI60..T VAI60.. VBI60..L VBI60..T For use in heating, ventilation, and air conditioning plants as shutoff or change- over ball valve. In closed circuits. ●...
  • Page 2 The brackets, premounted on the actuators, means you can mount them on the ball valves without tools. Technical design Design 1 Housing 2 Internally threaded connection 3 Seat 4 O-ring seal 5 Marble 6 Stem, squared 7 Slide clutch 8 O-ring seal Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 3 = Differential pressure over the fully opened ball valve and over the control v100 path at a volume flow V = Volume flow through the fully opened ball valve = 1 bar ≈ 10 mWS 100 kPa = 0.278 l/s water at 20 °C Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 4 To prevent cavitation in chilled water circuits, sufficient counter pressure must be supplied to the ball valve outlet, e.g. using an additional butterfly valve downstream of the ball valve. Maximum permissible differential pressure over the ball valve: See 80 °C curve in the above diagram. Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 5 A ─ AB Bypass B > 50 % of k Nominal size Flow nominal value for chilled water (5…30 °C) through a fully opened ball valve at a differential pressure of 100 kPa (1 bar) Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 6 S55845-Z174 Filter with internal threading ALX20 S55845-Z175 Filter with internal threading ALX25 S55845-Z176 Filter with internal threading ALX32 S55845-Z177 Filter with internal threading ALX40 S55845-Z178 Filter with internal threading ALX50 S55845-Z179 Filter with internal threading Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 7: Gma..9E

    GLB111.9E/MO AC 24 V Modbus RTU A6V10725318 GDB141.9E AC/DC 24 V 2 or 3 point 150 s A6V10636150 GDB341.9E AC 100...240 V Actuator type: Electromotive Open/close 2-wire SPDT (single pole double throw) While stock lasts Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 8: Table Of Contents

    Mounting instructions M4696 ASK77.3 (74 319 0648 0) Mounting instructions Mounting kit ASK77.5 Mounting instructions A6V11171911 (A5W00032790) Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 9 The reason is the high level of penetration at low surface tension of media based on potassium formate. Siemens rejects any and all liability for damages or consequential damages resulting from the use of this media together with our ball valves.
  • Page 10 A – B (B – A) = 100 % VBI60..T 3-port changeover ball valve with T 4214Z27 4214Z28 shaped A – AB = 100 % A – AB = 0 % B – AB = 0 % B – AB = 100 % Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 11 Adhere to all local and currently applicable laws and regulations. Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.
  • Page 12 (RoHS compliance, compositions, packaging, environmental benefits and disposal). Dezincification resistant Fittings for a product where PS x DN < 1000, do not require special testing and cannot have CE labeling See Section Product documentation [➙ 8] Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 13 [kg] VAI60.15-15 0.28 > 300 > 300 > 300 > 300 > 300 VAI60.20-22 0.36 VAI60.25-22 > 320 > 320 > 320 0.46 VAI60.32-35 > 320 > 320 VAI60.40-68 VAI60.50-96 > 335 > 335 1.74 Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 14 0.31 > 300 > 300 > 300 > 300 > 300 VBI60.20-16T 0.74 VBI60.25-16T > 320 > 320 > 320 0.63 VBI60.32-25T > 320 > 320 0.69 VBI60.40-49T 1.38 VBI60.50-73T > 335 > 335 2.26 Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 15 VAI60.15-15 > 300 > 300 > 300 > 300 > 300 ALI20VAI60 VAI60.20-22 ALI25VAI60/61 VAI60.25-22 > 320 > 320 > 320 ALI32VAI60/61 VAI60.32-35 > 320 > 320 ALI40VAI60/61 VAI60.40-68 ALI50VAI60/61 VAI60.50-96 > 335 > 335 Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 16 VBI60.15.. > 300 > 300 > 300 > 300 > 300 ALI20VBI60 VBI60.20.. ALI25VBI60/61 VBI60.25.. > 320 > 320 > 320 ALI32VBI60/61 VBI60.32.. > 320 > 320 ALI40VBI60/61 VBI60.40.. ALI50VBI60/61 VBI60.50.. > 335 > 335 Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 17 Filter Type Weight Inch ALX15 G ½ 0.178 ALX20 G ¾ 0.290 ALX25 0.410 ALX32 G 1¼ 0.680 ALX40 G 1½ 0.874 ALX50 1.428 ISO 228-1 Siemens CE1N4213en Smart Infrastructure 2020-02-20...
  • Page 18 VBI60.32-25T VAI60.40-68 VBI60.40-25L VBI60.40-49T VAI60.50-96 VBI60.50-37L VBI60.50-73T Issued by © Siemens Switzerland Ltd, 2010 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies...