Honeywell Prestige THX9000 System Installation Manual page 6

Thermostat with wireless accessories
Hide thumbs Also See for Prestige THX9000:
Table of Contents

Advertisement

Available languages

Available languages

Prestige™ Installation Guide
System-specific wiring guides
Heat pump systems
1H/1C Heat Pump [8]
C
24VAC common
R
Power [1]
Rc
[R+Rc joined by jumper]
O/B
Changeover valve [7]
Y
Compressor contactor
G
Fan relay
**
2H/1C Heat Pump [9]
C
24VAC common
R
Power [1]
Rc
[R+Rc joined by jumper]
O/B
Changeover valve [7]
Aux
Auxiliary heat relay
Y
Compressor contactor
G
Fan relay
**
L
Relay [12]
**
[See note on page 4]
[1] Power supply. Provide disconnect means and overload protection as required.
[2] Remove jumper (R to Rc) for systems with two transformers. Common connection
must come from cooling transformer.
[3] In Installer Setup, set system type to Heat Only, No Fan.
[4] In Installer Setup, set system type to Conventional with zero cooling stages.
[5] In Installer Setup, set system type to Conventional with zero heat stages.
[6] In Installer Setup, set system type to Conventional with 2 heat AND 2 cool stages.
[7] In Installer Setup, set changeover valve to O or B.
[8] In Installer Setup, set to Heat Pump with 1 compressor stage and no auxiliary heat stages.
[9] In Installer Setup, set to Heat Pump with 1 compressor stage and 1 auxiliary heat stage.
[10] In Installer Setup, set to Heat Pump with 2 compressor stages and no auxiliary heat stages.
[11] In Installer Setup, set to Heat Pump with 2 compressor stages and 1 auxiliary heat stage.
[12] "L" terminal sends a continuous output when thermostat is set to Em. Heat, and acts
as a system monitor when in Heat, Cool or Off modes.
**
**
6
2H/2C Heat Pump [10]
C
24VAC common
R
Power [1]
Rc
[R+Rc joined by jumper]
O/B
Changeover valve [7]
Y
Compressor contactor (stage 1)
Y2
Compressor contactor (stage 2)
G
Fan relay
**
3H/2C Heat Pump [11]
C
24VAC common
R
Power [1]
Rc
[R+Rc joined by jumper]
O/B
Changeover valve [7]
Aux
Auxiliary heat relay
Y
Compressor contactor (stage 1)
Y2
Compressor contactor (stage 2)
G
Fan relay
**
L
Relay [12]
See [notes] below.
**
**

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Prestige thx9321r01

Table of Contents