[ IX Disassembly Procedure ]
(4) Remove the four fan case fixing screws to take the top
half of the fan casing off.
Tighten screws to a torque of 1.4 0.2 N·m.

7. Heat exchanger

Exercise caution when removing heavy parts.
1. Remove the drain pan according to the procedure in section
4.
2. Remove the heat exchanger cover according to the proce-
dure in section 5-2.
3. Removing the cover
(1) Remove the five fixing screws on the cover (Q) to remove it.
Tighten screws to a torque of 2.0 0.2 N·m.
4. Removing the Heat exchanger
(1) Remove the fixing screws on the heat exchanger (R) to re-
move it.
Tighten screws to a torque of 1.4 0.2 N·m.
HWE20150
Fig.13
Fig.14
Fig.15
- 40 -
(Q)
(R)