Ordering Information - Honeywell V4730C Manual

Gas/air servo regulated gas valves
Hide thumbs Also See for V4730C:
Table of Contents

Advertisement

ORDERING INFORMATION

When purchasing replacement and modernization products from
your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering
number. If you have additional questions, need further informati-
on, or would like to comment on our products or services, please
write or phone:
1. Your local Honeywell Automation and Control Products Sales
Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada - Honeywell Limited/Honeywell Limitée, 35 Dynamic
Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the
world. Manufacturing in Australia, Canada, Finland, France, Ger-
many, Japan, Mexico, Netherlands, Spain, Taiwan, United King-
dom, U.S.A.
Opening Time:
Dead time maximum: 1 second.
First valve opening: less than 1 second.
Second valve opening: reaches 50% of the adjustable outlet
pressure within 5 seconds.
Maximum Allowable Leakage:
Outerwall: 3 cu. in./hr (50 cm3/h) at test pressure of 0.87 psi
(6 mBar) and 7.83 psi (540 mBar).
First Valve: 2.5 cu. in./hr (40 cm3/h) at test pressure of 0.87 psi
(6 mBar) and 7.83 psi (540 mBar).
Second Valve: 2.4 cu. in./hr (40 cm3/h) at test pressure of
0.87 psi (6 mBar) and 7.83 psi (540 mBar).
High Pressure Test:
In the OFF condition, the valve will withstand 21.75 psi (1.5 Bar)
inlet pressure without damage.
V4730C/V8730C/V4734C 1:1 Gas/Air Servo Regulated Gas Valves
Accessories:
FL020008 Mesh Screen.
Flange Kits (see Table 2).
DIN43650 Connector
32006653-001 Venturi O-rings/screws.
Operational Voltage Range:
The combination gas valve will function satisfactorily between
85% and 110% of the rated voltage.
Gas Valve Connection to Venturi (Field-Assembled):
Four screws and an O-ring are used to connect the gas valve to
the venturi/manual shutoff valve.
The metal tube provided with the venturi must be connected bet-
ween the venturi and the gas valve regulator.
Fan Connection:
The venturi is connected to the fan using six bolts (wich are inclu-
ded with VMU).
Minimum Load:
The minimum load for which the system can be used is
14-17% of the reference load, which equals a minimum
pressure differential of 0.2 in. wc (50 Pa) of the 1:1
venturi/servo regulator gas control.
Approvals:
Gas Appliance Directive 90.396/EEC
ANSI: Z21.21
CSA: 6.5
Capacity Curves:
See Fig. 9 to 14.
Dimensions:
See Fig. 1 to 5