Technical Data - ABB SPAU 331 C User Manual And Technical Description

Voltage relay
Table of Contents

Advertisement

Technical data

Energizing inputs
Rated voltage U
n
Terminal numbers
- phase-to-phase voltage U
- phase-to-phase voltage U
- phase-to-phase voltage U
- residual voltage U
0
Continuous voltage withstand
Burden at rated voltage U
Rated frequency f
, according to order
n
External control inputs
Terminal numbers
External control voltage
Current drain, typically
Contact outputs
Tripping outputs
Terminal numbers
- trip relay A
Rated voltage
Continuous current carrying capacity
Make and carry for 0.5 s
Make and carry for 3 s
Breaking capacity for dc when the control circuit
time constant L/R ≤40 ms at 48/110/220 V dc
Contact material
Signalling outputs
Terminal numbers
- alarm relay B
- alarm relay C
- alarm relay D
- alarm relay E
- self-supervision relay F
Rated voltage
Continuous current carrying capacity
Make and carry for 0.5 s
Make and carry for 3 s
Breaking capacity for dc when the control circuit
time constant L/R ≤40 ms at 48/110/220 V dc
Contact material
Auxiliary power supply
Voltage range of power supply modules:
SPGU 240 A1
- Nominal voltage U
n
- Operative range
SPGU 48 B2
- Nominal voltage U
n
- Operative range
Power consumption under quiescent/
operation conditions
12
23
31
n
100 V
110 V
13-14
13-15
16-17
16-18
19-20
19-21
28-29
28-30
2 x U
n
<0.5 VA
50 Hz or 60 Hz
10-11
18...265 V dc or 80...265 V ac
2...15 mA
65-66
250 V dc/ac
5 A
30 A
15 A
5A /3A /1 A
AgCdO
2
67-68-69
73-74-75
76-77-78
79-80-81
70-71-72
250 V dc/ac
5 A
10 A
8 A
1A /0.25A /0.25A
AgCdO
2
110/120/230/240 V ac
110/125/220 V dc
80...265 V ac/dc
24/48/60 V dc
18...80 V dc
10 W / 15 W
13