Expansion Valve Control; Basic Control - Hitachi SAMURAI Series Service Manual

Air cooled water chillers and air to water heat pump
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

2. Control Functions
Control of the cooling cycle

2.2.3 Expansion Valve Control

The expansion valve used in this product is an electronic expansion valve. The electronic expansion valve is composed by
the main unit and a coil. The control functions of the electronic expansion valve are as shown below.

1 Basic control

 0 (Zero) point adjustment
Compressor startup
¢ Starting control I
£ Starting control II
 Normal control
Compressor stop
 Stop control
10
 8
5
3
20      25    30
Cold water outlet setting temperature (ºC)
46
SMGB0082 rev.1 - 07/2015
Power ON
No
Yes
No
Yes
 0 (zero) point adjustment
0 (zero) point adjustment is conducted as an initialization
(detection of base point) upon power ON. This control is
performed to make the control pulses recognized by the
microprocessor and the actual pulse number to match at
0, by outputting a full closure order (under 0 pulse) for
the opening of the expansion valve. During execution,
the operation information of the LCD screen displays
"Adjusting 0 (zero) point of the expansion valve", while
the segment display becomes "Cn-E0" (n stands for unit
number).
¢ Startup control I
The opening is predetermined for 1 minute after
compressor startup.
£ Startup control II
The opening is controlled within a predetermined amount
of  variation  until  the  discharge  gas  superheat  (TdSH), 
which is calculated from the high pressure detected by
the high pressure sensor (Pd) and the discharge gas
temperature detected by the thermistor (Td) can be kept
above 10ºC.
 Normal control
The opening is controlled to achieve the target value of
suction  gas  superheat  (TsSH),  which  is  calculated  from 
the low pressure detected by the low pressure sensor
(Ps) and the suction gas temperature detected by the
thermistor (Ts).
Also, in the case of cooling operation, the target value of
TsSH  is  calculated  from  the  setting  value  of  cold  water 
outlet temperature, as shown in the figure below.
 Stop control
After compressor stop and setting to full closure, standby
at 0 pulses.
N O T E
The opening range used during the operation of the
expansion valve lies between 120 and 5960 pulses.