Hitachi SAMURAI Series Service Manual page 124

Condenserless water chillers
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

4. Troubleshooting
Troubleshooting by alarm code
SP-SP
Alarm code
Alarm stop reason
Pump operation feedback signal turns OFF while Pump operation signal (Y52P1) is ON. 
N O T E
It is enabled after establishment of interlock.
Pump operation feedback signal is not input within the time defined at "Waiting time for pump feedback" in optional 
functions. Or in case that Cold (hot) water inlet/outlet temperature differential exceeds 1.5ºC, and water conduction 
conditions have not been confirmed.
PCB monitoring position
PCBc (CPU PCB) PCN5
230V are being supplied between pin 1 and pin 
3 of connector PCN5 on PCBc (CPU PCB)
Yes
117
SMGB0097 rev.0 - 07/2015
Pump Interlock Abnormality
(PCB is normal)
The overcurrent 
No
relay for the pump 
(51P) is activated
The water is 
flowing
Temperature
difference between 
inlet water temperature 
thermistor and outlet water 
temperature thermistor is 
of less than 1.5ºC
Check PCBc (CPU PCB)
Examination of pump lock
Examination of pump
overcurrent relay
No
No
Check the wiring around 
the pump and the 
overcurrent relay for the 
Yes
No
Check of thermistors
Yes
4
pump