Siemens SITOP UPS1600 Equipment Manual page 153

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Energy storage
"Energy storage" has two different areas that depend on the battery type being used. First
select whether you are using a SITOP UPS1100 or SITOP BAT1600 battery module or some
other energy storage.
Using a SITOP BAT1600 or SITOP UPS1100 battery module
No additional parameterization.
Using a different battery module
Parameter
Battery type
Typical ambient temperature
Battery capacity
End-of-charge voltage at 20 °C
Temperature coefficient
Duration of the constant floating voltage charging phase
Charge current
Start preserve charge voltage
Stop buffering voltage
Faulty battery voltage
• Battery type
Make/type of battery: Pb ... lead-gel battery, pPb ... pure lead battery
• Typical ambient temperature
Typical ambient temperature of the battery in operation
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Value range
0 - 1
-70 - 100 °C
0.1 - 3,200 Ah
24 - 30 V
0 - 200 mV/K
0 - 720 h
0.001 - 3 or 4 or 5 A
23 - 30 V
18 - 23 V
1 - 18 V
Engineering and remote access
3.9 Web server
Default setting
0
40 °C
10 Ah
27.3 V
36 mV/K
12 h
0.3 A
25.20 V
18.50 V
6 V
153