Cooling Capacity Table - Panasonic WH-MXC09J3E8 Service Manual

Air-to-water heatpump
Hide thumbs Also See for WH-MXC09J3E8:
Table of Contents

Advertisement

19.3 Cooling Capacity Table

19.3.1
WH-MXC09J3E8
Water Out 7ºC
OD
Capacity(W)
16
9000
25
9000
35
9000
43
7200
19.3.2
WH-MXC12J9E8
Water Out 7ºC
OD
Capacity(W)
16
11400
25
12000
35
12000
43
10300
Input
Current(A)
Capacity(W)
Power(W)
1660
2.5
2060
3.1
2910
4.3
3360
5.0
Input
Current(A)
Capacity(W)
Power(W)
2150
3.2
2930
4.4
4230
6.3
5000
7.5
Water Out 14ºC
Input
Current(A)
Power(W)
11000
1540
12600
2450
10900
3070
8700
3330
Water Out 14ºC
Input
Current(A)
Power(W)
13600
2140
15700
3680
13600
4440
11800
5090
213
Water Out 18ºC
Input
Capacity(W)
Power(W)
2.3
11400
1350
3.7
10500
1600
4.6
9000
2020
5.0
7300
2530
Water Out 18ºC
Input
Capacity(W)
Power(W)
3.2
15000
2150
5.5
14000
2660
6.6
12000
3170
7.6
10400
3870
Current(A)
2.0
2.4
3.0
3.8
Current(A)
3.2
4.0
4.7
5.8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-mxc12j9e8

Table of Contents