Access Actuator - Huawei SmartDC V100R021C10 User Manual

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
The emergency button or emergency door release button is used to open a door in
emergencies.

3.2.4.1.1 Access Actuator

The access actuator is the control component for the aisle door in a smart module.
It connects to the ECC800-Pro controller over FE port, wireless networking
(802.15.4). It opens the magnetic lock by detecting the card swiping information
of the card reader, door open button information, and fire linkage information. It
has access right management, access event record, and alarm record functions.
Figure 3-10 Access actuator
(1) 48 V power port
(4) RS485 port COM1
(7) BLINK button
(10) AI/DI_2 dry contact
(reserved port for linkage
control or third-party fire
extinguishing system dry
contacts)
Issue 04 (2021-10-09)
The emergency button can disconnect the power supply to the lock and
therefore unlock the door in case of emergency.
In case of emergency, break the glass of the emergency door release button
to disconnect the power supply to the lock and therefore unlock the door.
Copyright © Huawei Technologies Co., Ltd.
(2) PoE port
(5) Address DIP switch
(8) WG_2 Wiegand interface (9) WG_1 Wiegand interface
(11) AI/DI_1 dry contact
(reserved port for exit
button)
3 Device Description
(3) RS485 port COM2
(6) Status indicator
(12) LOCK/GND/GATE/COM door
status or magnetic lock port
34

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800

Table of Contents