LG MULTI V WATER MINI Engineering Manual page 56

Table of Contents

Advertisement

WATER CIRCUIT INSTALLATION
Variable Water Flow Control Kit (Required Accessory)
Variable Water Flow Control Kit DIP Switch Settings
Using 'SWDIP', select the control function using the DIP switches as described below.
Figure 30: DIP Switch Setting.
ON
OFF
Default is L1: ON, L2: OFF.
Table 24: Output Signal Setting.
Table 25: RS-485 Communication Function Setting.
• After the DIP switch is changed, the reset switch must be pressed to reflect the setting.
• Before operating the water source unit, check the water flow rate and the PCB voltage signal.
• Minimum flow rate range is 50%; Reference flow rate: 4.4-ton - 15.9 gpm.) When the Variable Water Flow Control kit is also installed, set
the flow switch minimum flow rate to 40% of the nominal flow rate instead of 50%. If the flow rate is lower, it will damage the water source
unit.
56 | WATER CIRCUIT
L1 2 3
4
DIP Switch Setting
ON
OFF
L1 2 3
4
ON
OFF
L1 2 3
4
ON
OFF
L1 2 3
4
ON
OFF
L1 2 3
4
DIP Switch Setting
ON
OFF
L1 2 3
4
ON
OFF
L1 2 3
4
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Function
Control signal : DC 0V(OFF), DC 8~10V(ON)
Control signal : DC 0V(OFF), DC 6~10V(ON)
Control signal : DC 0V(OFF), DC 4~10V(ON)
Default status
Control signal : DC 0V(OFF), DC 2~10V(ON)
Function
RS-485 communication function enable
RS-485 communication function disable