High-Seismic Target And Seal-In Unit; Installation; Servicing - GE CCP13E Instructions Manual

Three-phase power-directional relay
Table of Contents

Advertisement

Clutch
The clutch should not slip at rated voltage and 10 amperes when the relay is
connected as in Figure 2. See the
HIG H-SEISMIC TARGET AND SEAL-IN UNIT
The target and seal-i n unit has an operat ing coil tapped at 0.2 and 2.0 ampere s.
The relay is shipped from the factory with the tap screw in the higher ampere
The tap screw is the screw holding the right-han d stationar y contact. To
position.
change the tap setting, first remove one screw from the left-han d stationa ry contact
and place it in the desired tap.
place it on the left-hand stationary contact where the first screw was removed.
This procedure is necessary to prevent the right-hand stationary contact
Figure 8.
from getting out of adjustmen t.
same time.
Pickup and Dropout Test
1.
Connect relay terminals 1 and 11 to a DC source using a load box to control the
current over a range of 0.1 to 2 amperes.
2.
Close the left contact manually.
3.
Increase the current slowly until the seal-in unit picks up.
The target must latch in.
4.
Decrease the current slowly until the seal-in unit drops out.
The target must remain latched in.
again .
2.0
The location of the relay should be clean and dry, free from dust, excessive heat
and vibration, and should be well-lighted to facilitate inspection and testing.
The relay should be mounted on a vertical surface.
dimens ion s are shown in Figure 3.
The internal connections of the CCP13E are shown in Figure 5. An elementary diagram
of typical external connections is shown in Figure 2.
One of the mountin g studs or screws should be permanently grounded by a conductor
not less than No.12 B&S gauge copper wire or its equivalent.
GEK-65525

SERVICING

section for clutch adjustment.
Next remove the screw from the undesired tap and
Screws should
never
Reset the target before checking pickup
TABLE IV
0.12 - 0.20
1.2 - 2.0

INSTALLATION

10
be left in
both
See Table IV.
See Table IV.
Dropout Current
0.05 or more
0.50 or more
The outline and panel-drilling
See
taps at the