Order No. SBPAC1403010CE VRF SYSTEMS INDOOR UNIT 4-Way Cassette Ceiling Low Silhouette Ducted (U1 type) (T2 type) (F2 type) Indoor Unit Class 4-Way Cassette S-22MU1E5A S-28MU1E5A S-36MU1E5A S-45MU1E5A S-56MU1E5A S-60MU1E5A S-73MU1E5A S-90MU1E5A S-106MU1E5A S-140MU1E5A S-160MU1E5A 4-Way Cassette S-15MY2E5A S-22MY2E5A S-28MY2E5A...
Page 2
Design of VRF SYSTEM 1. Electrical Wiring 1-1. General Precautions on Wiring Before wiring, confirm the rated voltage of the unit as shown Regulations on wire diameters differ from locality to on its nameplate, then carry out the wiring closely following locality.
Page 3
Design of VRF SYSTEM 1. Electrical Wiring 1-3. Wiring System Diagrams Indoor unit (No. 1) Outdoor unit Power supply 220/230/240V ~50/60Hz Ground Remote To outdoor unit controller Ground Ground Indoor unit (No. 2) Power supply Ground 220/230/240V ~50/60Hz Ground Remote controller Ground Indoor unit...
Page 4
Design of VRF SYSTEM 1. Electrical Wiring CAUTION When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug.
Page 5
Design of VRF SYSTEM 1. Electrical Wiring (5) Use shielded wires for inter-unit control wiring (c) and Shielded wire ground the shield on both sides, otherwise misoperation from noise may occur. (Fig. 2-5) Connect wiring as shown in Section “1-3. Wiring System Ground Ground Fig.
Page 6
Design of VRF SYSTEM 1. Electrical Wiring Wiring sample U1 type Fasten tightly. Clamper* Clamper* Remote Control Wiring Inter-unit Control Wiring Power Supply Clamper* Clamping Clip Use this screw when connecting the shield Protective ground screw for the Inter-unit control wiring to ground. (External Solenoid Valve Kit for 3WAY) Functional ground screw (External Electronic Expansion Valve Kit and Schedule Timer)
Page 7
Design of VRF SYSTEM 2. SELECTING THE INSTALLATION SITE 2-3. Low Silhouette Ducted (F2 type) AVOID: areas where leakage of flammable gas may be expected. 25 cm places where large amounts of oil mist exist. direct sunlight. 25 cm locations near heat sources which may affect the performance of the unit.
Page 8
VRF SYSTEMS Indoor Unit Specifi cations Contents 4. VRF SYSTEMS INDOOR UNIT SPECIFICATIONS 1. 4-Way Cassette Type (U1 Type) ..................1-1. Specifications .........................4-2 1-2. Major Component Specifications..................1-3. Dimensional Data ......................4-17 1-4. Noise Criterion Curves ....................4-20 1-5. Air Flow Distance / Temperature Chart ............... 4-22 2.
Page 9
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-1. Specifi cations Unit specifi cations (A) INDOOR MODEL S-15MF2E5A S-22MF2E5A S-28MF2E5A PANEL MODEL PERFORMANCE TEST CONDITION ISO15042 / AS / NZS3823 / EN14511 / EN12102 ø, Hz 1ø...
Page 10
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-1. Specifi cations Unit specifi cations (B) INDOOR MODEL S-36MF2E5A S-45MF2E5A S-56MF2E5A PANEL MODEL PERFORMANCE TEST CONDITION ISO15042 / AS / NZS3823 / EN14511 / EN12102 ø, Hz 1ø...
Page 11
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-1. Specifi cations Unit specifi cations (C) INDOOR MODEL S-60MF2E5A S-73MF2E5A S-90MF2E5A PANEL MODEL PERFORMANCE TEST CONDITION ISO15042 / AS / NZS3823 / EN14511 / EN12102 ø, Hz 1ø...
Page 12
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-1. Specifi cations Unit specifi cations (D) INDOOR MODEL S-106MF2E5A S-140MF2E5A S-160MF2E5A PANEL MODEL PERFORMANCE TEST CONDITION ISO15042 / AS / NZS3823 / EN14511 / EN12102 ø, Hz 1ø...
Page 13
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-2. Major Component Specifications Indoor unit (A) MODEL No. S-15MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5910 (Microprocessor) Fan (Number...diameter) Sirocco Fan (1...ø185) Fan motor Model...Nominal output...
Page 14
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (B) MODEL No. S-22MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5910 (Microprocessor) Fan (Number...diameter) Sirocco Fan (1...ø185) Fan motor Model...Nominal output SIC-70CW-D8120-1...119 W...
Page 15
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (C) MODEL No. S-28MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5911 (Microprocessor) Fan (Number...diameter) Sirocco Fan (1...ø185) Fan motor Model...Nominal output SIC-70CW-D8120-1...119 W...
Page 16
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (D) MODEL No. S-36MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5912 (Microprocessor) Fan (Number...diameter) Sirocco Fan (1...ø185) Fan motor Model...Nominal output SIC-70CW-D8120-1...119 W...
Page 17
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (E) MODEL No. S-45MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5913 (Microprocessor) Fan (Number...diameter) Sirocco Fan (1...ø185) Fan motor Model...Nominal output SIC-70CW-D8120-1...119 W...
Page 18
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (F) MODEL No. S-56MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5914 (Microprocessor) Fan (Number...diameter) Sirocco Fan (1...ø185) Fan motor Model...Nominal output SIC-70CW-D8120-1...119 W...
Page 19
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (G) MODEL No. S-60MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5915 (Microprocessor) Fan (Number...diameter) Sirocco Fan (2...ø185) Fan motor Model...Nominal output SIC-70CW-D8120-2...124 W...
Page 20
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (H) MODEL No. S-73MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5916 (Microprocessor) Fan (Number...diameter) Sirocco Fan (2...ø185) Fan motor Model...Nominal output SIC-70CW-D8120-2...124 W...
Page 21
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit ( I ) MODEL No. S-90MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C6405 (Microprocessor) Fan (Number...diameter) Sirocco Fan (2...ø185) Fan motor Model...Nominal output SIC-70CW-D8120-2...124 W...
Page 22
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (J) MODEL No. S-106MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5917 (Microprocessor) Fan (Number...diameter) Sirocco Fan (3...ø185) Fan motor Model...Nominal output SIC-101CW-D8200-1...235 W...
Page 23
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (K) MODEL No. S-140MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5918 (Microprocessor) Fan (Number...diameter) Sirocco Fan (3...ø185) Fan motor Model...Nominal output SIC-101CW-D8200-1...235 W...
Page 24
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor unit (L) MODEL No. S-160MF2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C5919 (Microprocessor) Fan (Number...diameter) Sirocco Fan (3...ø185) Fan motor Model...Nominal output SIC-101CW-D8200-1...235 W...
Page 25
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-3. Dimensional Data Indoor unit: S-15MF2E5A/22MF2E5A/28MF2E5A/36MF2E5A/45MF2E5A/56MF2E5A/60MF2E5A/ 73MF2E5A/90MF2E5A/106MF2E5A/140MF2E5A/160MF2E5A Unit: mm Type 15, 22, 28, 36, 45, 56 450 (Pitch 150 × 3) 60, 73, 90 1,067 1,000 750 (Pitch 150 × 5) 106, 140, 160 1,467 1,400...
Page 26
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Flange for Air Intake Duct (Field supply) For Low Silhouette Ducted Type unit: pieces Preparation before installation Prior to installation, flange material for air intake duct must have a minimum Indoor unit type thickness of 1.0mm or more.
Page 27
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-4. Noise Criterion Curves Both 50Hz and 60Hz High MODEL : S-15MF2E5A MODEL : S-22MF2E5A SOUND LEVEL HIGH 33 dB(A) SOUND LEVEL HIGH 33 dB(A) 22 dB(A) 22 dB(A) CONDITION 1.5 m directly below unit...
Page 28
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Both 50Hz and 60Hz High MODEL S-60MF2E5A MODEL S-73MF2E5A SOUND LEVEL HIGH 35 dB(A) SOUND LEVEL: HIGH 35 dB(A) 26 dB(A) 26 dB(A) CONDITION: 1.5 m directly below unit CONDITION 1.5 m directly below unit NC-50...
Page 29
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-5. External Static Pressure Setting Choose one of the following methods from “a”, “b”, “c” or “d” as shown in the flow chart (within the dotted lines) and then make the setting accordingly.
Page 30
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) (3) Refer to Table 2-2 and Fig. 2-2 for details on the relationship between the value of item code “b0” and the external static pressure. (4) When set in group control (connecting multiple indoor units with one wired remote controller), set each indoor unit to item code “b0”. When amending the setting after selecting [ b.
Page 31
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) 2-5-2. Operating the Timer Remote Controller (CZ-RTC2) Table 2-2 Setting the external static pressure 2-5-2-1. Setting Item Code “ ” Indoor unit Item code 15, 22, 28, 36, 45, 106, 140, 160 Press and hold down the buttons...
Page 32
VRF SYSTEMS Indoor Unit Specifi cations 2. Low Silhouette Ducted Type (F2 Type) Indoor Fan Performance 90 type Item code “ ” PQ diagram M M M M M M M L L L L 1 -3 1 -2 L L L L 1 -2 L L L L Airflow Volume (m...
Page 33
VRF SYSTEMS Indoor Unit Specifi cations 7. Fresh Air Intake 7-1. Precautions Regarding External Air Intake (1) Ventilation Load Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is involved. (2) Restrictions on External Air Intake Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of the indoor unit and the intake method.
Page 34
VRF SYSTEMS Indoor Unit Specifi cations 7. Fresh Air Intake 7-2. External Air Intake Volume & Resistance Within Unit / Operation Noise Characteristics (continued) Low Silhouette Ducted (F2 Type) 7-2-4. In a Case of External Air Intake to Unit Directly (Using external air intake cylindrical flange) Operation noise Resistance within the unit (External air intake only)
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM 1-6. Low Silhouette Ducted Type (F2 Type) S-15MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit.
Page 39
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-22MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 2.2 kW AIR FLOW RATE : 14.0 m...
Page 40
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-28MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 2.8 kW AIR FLOW RATE : 14.0 m...
Page 41
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-36MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 3.6 kW AIR FLOW RATE : 14.0 m...
Page 42
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-45MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 4.5 kW AIR FLOW RATE : 14.0 m...
Page 43
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-56MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 5.6 kW AIR FLOW RATE : 16.0 m...
Page 44
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-60MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 6.0 kW AIR FLOW RATE : 21.0 m...
Page 45
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-73MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 7.3 kW AIR FLOW RATE : 21.0 m...
Page 46
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-90MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 9.0 kW AIR FLOW RATE : 25.0 m...
Page 47
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-106MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 10.6 kW AIR FLOW RATE : 32.0 m...
Page 48
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-140MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 14.0 kW AIR FLOW RATE : 34.0 m...
Page 49
Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-160MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 16.0 kW AIR FLOW RATE : 36.0 m...
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM 2-6. Low Silhouette Ducted Type (F2 Type) S-15MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit.
Page 51
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-22MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 2.2 kW AIR FLOW RATE : 14.0 m...
Page 52
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-28MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 2.8 kW AIR FLOW RATE : 14.0 m...
Page 53
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-36MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 3.6 kW AIR FLOW RATE : 14.0 m...
Page 54
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-45MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 4.5 kW AIR FLOW RATE : 14.0 m...
Page 55
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-56MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 5.6 kW AIR FLOW RATE : 16.0 m...
Page 56
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-60MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 6.0 kW AIR FLOW RATE : 21.0 m...
Page 57
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-73MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 7.3 kW AIR FLOW RATE : 21.0 m...
Page 58
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-90MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 9.0 kW AIR FLOW RATE : 25.0 m...
Page 59
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-106MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 10.6 kW AIR FLOW RATE : 32.0 m...
Page 60
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-140MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 14.0 kW AIR FLOW RATE : 34.0 m...
Page 61
Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-160MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 16.0 kW AIR FLOW RATE : 36.0 m...
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM 3-6. Low Silhouette Ducted Type (F2 Type) S-15MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit.
Page 63
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-22MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 2.2 kW AIR FLOW RATE : 14.0 m...
Page 64
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-28MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 2.8 kW AIR FLOW RATE : 14.0 m...
Page 65
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-36MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 3.6 kW AIR FLOW RATE : 14.0 m...
Page 66
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-45MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 4.5 kW AIR FLOW RATE : 14.0 m...
Page 67
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-56MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 5.6 kW AIR FLOW RATE : 16.0 m...
Page 68
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-60MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 6.0 kW AIR FLOW RATE : 21.0 m...
Page 69
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-73MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 7.3 kW AIR FLOW RATE : 21.0 m...
Page 70
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-90MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 9.0 kW AIR FLOW RATE : 25.0 m...
Page 71
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-106MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 10.6 kW AIR FLOW RATE : 32.0 m...
Page 72
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-140MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 14.0 kW AIR FLOW RATE : 34.0 m...
Page 73
Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-160MF2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 16.0 kW AIR FLOW RATE : 36.0 m...