Dimensional Drawings:
Installation:
1
4
Step 1: Place a flat blade screwdriver and pull up gently the diffusor's clips from both sides to remove the
diffusor.
Step 2: Place a flat blade screwdriver and pull up gently the reflector.
Step 3: Install the plastic base with the included mounting screws and plugs. If the hole that exists is not
useful, drill another hole on one of the designated positions in order to pass the cables and install
the included gasket (verify that are not deformed).
Step 4: Set the module address. For more information about module settings see the next page.
Step 5: Always use in any case round mains cable, with a diameter of 5-10mm. ATTENTION!! The cable
must not be deformed in any way (This requirement is important to ensure the IP rating). Make a
hole in the center by using a small screwdriver. Pass the round cable through the gasket.
Step 6: Connect the mains cable to the respective terminal block: L for live wire, N for neutral. Install the
included tie (if needed) to fasten securely the power cables. Power supply cables cross section
should be 0.8 – 3 mm .
Step 7: Refit carefully the removed parts (Step 1 & 2). The diffusor must be secured (click sound). This
requirement is important to ensure the IP65 rating.
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
ImperLED E
Addressable CBS Emergency Light
2
5
2
3
6
N
L
http://www.hls-nordic.com
GB

Advertisement

loading

Summary of Contents for Honeywell ImperLED E

  • Page 1 0.8 – 3 mm . Step 7: Refit carefully the removed parts (Step 1 & 2). The diffusor must be secured (click sound). This requirement is important to ensure the IP65 rating. Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com...
  • Page 2 Wall installation Wall Ceiling bottom view ImperLED luminaries can be surface mounted on walls or ceilings. Mounting Accessories (Available After Request) 290405.11 ImperLED Suspended Pictogram 290471 ImperLED Wall Bracket Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com...
  • Page 3 The light source contained in this luminary shall only be replaced by the manufacturer, or his agent, or a similar qualified person. NOTE! The light source is non-user replaceable. Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com...
  • Page 4 SET010 select Technical description 78 x 30 x 20 Dimensions (L x W x H in mm) Temperature: -30°C up to +60°C, T =+75°C cmax Cross section: Max: 1.5mm Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway http://www.hls-nordic.com...