7
7
1 2 3 4
1 2 3 4
1h
3h
(default position)
1 2 3 4
Switch 4 = ON
Maintained operation
(default position)
Step 7: The control of maintained or non maintained operation of the luminary is achieved through Switch
4 of DS1. For maintained operation, switch number 4 must be in ON position. For non-maintained
operation, switch number 4 must be in OFF position.
The user can select one of the 3 available minimum autonomy durations: 1 hour, 3 hours and 8 hours. The
selection must be done while the luminaire is disconnected from AC and battery supplies. The selection is
achieved through Switches 2 & 3 of DS1. Switch 1 is not used.
Two additional labels are included in the package, one for 3 hour duration (180) and one for 8 hour duration
(480). Depending on the selected duration, the installer must cover the default 1 hour (60) printing with
one that has the required duration.
Step 8: Slide the two aluminium parts carefully together.
Step 9: Fasten the two screws (included) as shown in the picture.
Step 10: Fasten the two screws (included) as shown in the picture.
Description
Indicator LEDs
Normal
Charging (battery test not possible while charging
Mains off, battery not connected or charger fault
Battery test
Battery fault
Light source test
Light source fault
Battery fault and light source fault
LED Status explanation
Off
On
Note: In case of mains power disconnection for a period of more than two months, the battery must be
disconnected.
Note: In case of battery replacement, this must be replaced with parts of the same type and characteristics.
The replacement must be performed by the manufacturer or a competent person.
Note: If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person
in order to avoid hazard.
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
8
10
1 2 3 4
8h
1 2 3 4
Switch 4 = OFF
Non-maintained
operation
Flashing
At the end of their useful life the packaging, product
and batteries should be disposed of via a suitable
recycling centre. Do not dispose of with your normal
household waste. Do not burn.
Important notice when installing luminaires within
the same area!!!
To avoid that luminaires perform their battery test at
the same day, connect the battery packs with more
than 1,5 minutes inbetween.