Appendix B: System 5000 (Ul 8Th); B.1: Capabilities; B.2: Installation Requirements - Honeywell NOTIFIER LDM Series Instruction Manual

Lamp driver module
Table of Contents

Advertisement

NOTE: The LDM begins annunciation of circuits on the module installed directly after the CPU-5000. To ensure full employment of LDM
points, mount the modules that need lamp driver annunciation in the CPU row first, then in the second row, etc. Modules with circuits that
are not to be annunciated by the LDM-32 should be installed further down in the cabinet.
B.1 Capabilities
When installed with a System 5000, the LDM Series modules can annunciate the status of initiating and notification circuits, relays, and
several system control functions. Each lamp driver output is automatically assigned to one and only one system I/O point:
Optional System 5000 plug in Modules
IZM-8 - Initiating Device Circuits (alarm and trouble)
AIM-200 Zones (alarm and trouble)
ICM-4/ICE-4 - Notification Appliance Circuits (trouble)
CRM-4/CRE-4 - Control Relay Modules
TCM-2/TCM-4 - Time Control Modules
VCM-4/VCE-4
DCM-4
System Control Switches
Acknowledge
Signal Silence
System Reset
Activate selected system outputs (notification circuits, relays)
Trouble Indication
Communication between the CPU and the LDMs is accomplished over a two-wire EIA-485 serial communication bus. The EIA-485 bus
is supervised by the System 5000. Loss of communication results in System Trouble and Module Failure indications at the CPU.
Lamp/LED Driver Operation
Lamp Driver outputs do not latch - they track or follow the status of each zone/point that they are assigned to annunciate. Table B.1
defines the ON status of each Lamp Driver output.
Software Required
For the LDM to function properly, the CPU must be operating under ROM1-5000 Part Number 73085 (or higher).
Programming for Remote Annunciation
After complete installation, the LDM must be programmed into the System 5000 before it will function. Program the LDM as if it were
an annunciator. Refer to the System 5000 Programming Manual, Document 15584.
B.2 Installation Requirements
The EIA-485 circuit that communicates with the LDM must be connected to the CPU as illustrated below. The CPU must be Revision D
or greater. The revision level of the CPU is marked on a label affixed to the upper board.
LDM Series Instruction Manual — P/N 15885:H3 8/12/2019

Appendix B: System 5000 (UL 8th)

Supervised and
Power-Limited
Figure B.1 Connecting the EIA-485 Loop to the CPU-500
EIA-485 (-)
(+) EIA-485
to LDM TB2-4
to LDM TB2-1
System 5000CPU
31