Hitachi UTOPIA R32 Series Technical Catalogue page 112

Table of Contents

Advertisement

10 Electrical wiring
DIP and RSW switches settings

DSW5: Transmission setting of end terminal resistance
In the case that the outdoor units quantity in the same H-LINK is 2 or more, set No. 1 pin of DSW5 at "OFF" side from the
2nd refrigerant group outdoor unit. If only one outdoor unit is used, no setting is required.
Setting for transmission
It is required to set the outdoor unit number refrigerant cycle and end terminal resistance for the H-LINK.
In the same refrigerant cycle, set the same refrigerant cycle number for the outdoor unit and the indoor units.
Example incase of setting before cycle number 25
DSW4: Turn ON pin number 2
RSW1: set dial number 5
Outdoor unit
DSW5
1 2
Control wiring
(H-LINK II or
H-LINK)
Indoor
Indoor
unit
104
TCGB0136 rev.1 - 05/2021
Factory setting
Cancellation
Turn OFF DSW5 number 1 pin for cancel of
end terminal resistance setting
Outdoor unit
DSW5
1 2
Control wiring
(H-LINK II or H-LINK)
unit
0
Outdoor unit
DSW5
1 2
Control wiring
(H-LINK II or H-LINK)
Indoor
unit
Outdoor unit
DSW5
1 2
Indoor
unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents