HPSR101
RESIDEO HYDRONIC PRO
SWITCHING RELAY
PANEL SPECIFICATIONS
OS Numbers
Transformers
HPSR101
(1) 24V 15VA
NOTES:
1.
All circulator relay connections are rated for 5A full load and 30A locked rotor (1/6 to 1/2HP depending on
technology) at 120VAC. Check circulator plate ratings to ensure full load current is not exceeded.
2.
All thermostat connections supply a 24V Class 2 output.
WHAT'S IN THE BOX?
• Hydronic Switching Relay
• Mounting Hardware (3 Screws and 3 Wall Anchors)
• 1, 1-Amp Fuse; 1, 6-Amp Fuse
• Install Manuals (English & French)
Table 1.
Input Power
Pump Fuse
120VAC, 60Hz, 1
INSTALLATION INSTRUCTIONS
CAUTION
1. Disconnect power supply before beginning
installation to prevent electrical shock or
equipment damage.
2. Use copper conductors only.
3. Use only NEC Class 1 wire for all line voltage
wiring connections. Class 1 wires must be
rated for at least 167 °F (75 °C).
4. For installation by professionals only.
Width
6 Amp
5-1/8"
Type 1 Enclosure
Height
Depth
6-3/4"
2-3/8"
33-00349EF-06

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell HPSR101

  • Page 1 HPSR101 RESIDEO HYDRONIC PRO SWITCHING RELAY INSTALLATION INSTRUCTIONS WHAT'S IN THE BOX? • Hydronic Switching Relay • Mounting Hardware (3 Screws and 3 Wall Anchors) • 1, 1-Amp Fuse; 1, 6-Amp Fuse • Install Manuals (English & French) CAUTION 1. Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
  • Page 2: Wiring And Setup

    HPSR101 MOUNTING WIRING AND SETUP Hang Hole Flow Power Input 1. Hang the panel on a wall-mounted screw. Resideo Hydronic Panels include a convenient wiring terminal for wiring 120V/60Hz/1Ph power. These terminals, found at the bottom left side of the panel, provide power to the transformer and all pumps installed on the system.
  • Page 3 HPSR101 Standard Wiring Layout Below wiring diagrams represent two common ways to wire a Switching Relay. THERMOSTAT WIRING NON-CONNECTED OR POWER STEALING 1 AMP FUSE ALL TRANSFORMER R W C CONNECTIONS ARE FACTORY WIRED POWER IN 24VAC, 24 VAC 15VA...
  • Page 4: Troubleshooting

    The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates. Tous droits réservés. La marque de commerce Honeywell Home est utilisée avec l’autorisation d’Honeywell International, Inc. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées.
  • Page 5: Contenu De L'emballage

    HPSR101 RELAIS DE COMMUTATION HYDRONIQUE PRO RESIDEO INSTRUCTIONS D’INSTALLATION CONTENU DE L’EMBALLAGE • Relais de commutation hydronique • Quincaillerie de montage (3 vis et 3 ancrages muraux) • 1 fusible de 1 A; 1 fusible de 6 A • Manuels d’installation (anglais et français) MISE EN GARDE 1.
  • Page 6: Montage

    HPSR101 MONTAGE Transformateur Ce panneau fournit un transformateur de 24 V, 15 VA pour alimenter le thermostat. Le transformateur peut être Trou de suspension remplacé en cas de défectuosité. Pour ce faire, retirez les vis de montage et installez un nouveau transformateur.
  • Page 7 HPSR101 Disposition standard du câblage Les schémas de câblage ci-dessous représentent deux façons classiques de raccorder un relais de commutation. CÂBLAGE DU THERMOSTAT SANS LE FIL C FUSIBLE DE 1 A TOUS LES RACCORDEMENTS DU TRANSFORMATEUR R W C SONT RÉALISÉS EN USINE 24 V c.a.
  • Page 8: Dépannage

    The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates. Tous droits réservés. La marque de commerce Honeywell Home est utilisée avec l’autorisation d’Honeywell International, Inc. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées.

This manual is also suitable for:

Hpsr104/uHydronic pro hpsr101

Table of Contents