[ VIII Disassembly Procedure ]
4. Drain pump
1. Remove the fixing screws shown in Fig. 1, and remove
the control box cover.
2. Remove the connector from CN4F and CNP on the con-
trol board, shown in Fig. 2.
3. Remove the fixing screws shown in Fig. 3, and remove
the maintenance cover.
4. Remove the fixing screws holding the drain hose and the
drain pump assy shown in Fig. 4.
5. Remove the fixing screws and cut the band shown in Fig.
5, by doing so, the drain pump and the float switch can be
disassembled.
HWE1804A
Control box cover
Fixing screw
Fixing screw
Fig.1
Wire saddle
Indoor
P.C. board
CN4F White
CNP White
Band
Fig.2
Fig.3
Fig.4
Band
Fig.5
- 27 -
Fixing screw
Float switch wire
(clear wire)
Wire saddle
SW1
Drain pump wire
(Black wire)
Maintenance
cover
Fixing screws
GB