Phase reversal protection PREVPTOC

The phase reversal protection is used for detecting the reversed connection of the
phases to a three-phase motor by monitoring the negative-phase sequence current
of the motor.
The operation of the function is based on the detection of very high negative-
sequence currents during motor start up due to incorrect phase connections to the
motor. The condition causes the motor to rotate in the reverse direction. The
function starts and operates when the negative-sequence current exceeds the
corresponding set limits. Phase reversal protection is blocked when current circuit
supervision detects a failure. Operate signal is used to trigger the disturbance recorder.

Motor negative-sequence overcurrent protection MNSPTOC

Two instances of negative-sequence overcurrent detection are provided for
protection against single-phasing, unbalance load or unsymmetrical voltage. The
set of three phase currents, I3P, is connected to the inputs.
The function operates in two modes, the definite time mode (DT) and the inverse
definite minimum time (IDMT) mode, for which two instances of the function
block are used. The negative-sequence overcurrent protection is blocked in case of
current circuit supervision failure is activated.
The common operate and start signal from the both MNSPTOC functions are
connected to an OR-gate to form a combined negative-sequence overcurrent
operate and start signal which is used to provide a LED indication on the LHMI.
Also separate start and operate signal from the both MNSPTOC functions is
connected to the disturbance recorder.